🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

40 Amp Wire Size at 30 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 40 A load over a 30 ft (9.1 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 0.34%
Aluminum Wire (≤3% Drop)8 AWGDrop: 2.67V (0.56%)
Voltage at Load End478.4 VLoss: 1.62 V (112.2 W)
Power & Breaker (125%)33.26 kW50A Breaker Recommended

All AWG & kcmil Wire Gauges for 40 Amps at 30 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A6.52 V (1.36%)473.5 V10.75 V (2.24%)451.6 WDrop/Amp High
12 AWG3.31 mm²20 A4.1 V (0.85%)475.9 V6.76 V (1.41%)283.8 WDrop/Amp High
10 AWG5.26 mm²30 A2.58 V (0.54%)477.4 V4.25 V (0.89%)178.6 WDrop/Amp High
8 AWG8.37 mm²50 A1.62 V (0.34%)478.4 V2.67 V (0.56%)112.2 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A1.02 V (0.21%)479.0 V1.68 V (0.35%)70.6 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A0.64 V (0.13%)479.4 V1.06 V (0.22%)44.4 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.51 V (0.11%)479.5 V0.84 V (0.17%)35.2 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.4 V (0.08%)479.6 V0.67 V (0.14%)27.9 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.32 V (0.07%)479.7 V0.53 V (0.11%)22.1 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.25 V (0.05%)479.7 V0.42 V (0.09%)17.6 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.2 V (0.04%)479.8 V0.33 V (0.07%)13.9 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.16 V (0.03%)479.8 V0.26 V (0.05%)11.0 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.13 V (0.03%)479.9 V0.21 V (0.04%)8.8 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.11 V (0.02%)479.9 V0.18 V (0.04%)7.4 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.09 V (0.02%)479.9 V0.15 V (0.03%)6.2 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.08 V (0.02%)479.9 V0.13 V (0.03%)5.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.07 V (0.01%)479.9 V0.11 V (0.02%)4.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.05 V (0.01%)479.9 V0.09 V (0.02%)3.7 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.04 V (0.01%)480.0 V0.07 V (0.02%)3.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.04 V (0.01%)480.0 V0.06 V (0.01%)2.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.03 V (0.01%)480.0 V0.04 V (0.01%)1.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 40 amps at 30 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 40A load over 30 feet one-way at 480V (3-Phase), you need 8 AWG copper wire. This produces a voltage drop of 1.62V (0.34%) and delivers 478.4V at the load.

What size aluminum wire is required for 40 amps at 30 feet?

Using aluminum conductors (75°C rating), you should use 8 AWG to maintain voltage drop at 2.67V (0.56%).

What breaker size is needed for a 40A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (40A × 1.25 = 50.0A), which corresponds to a standard 50A circuit breaker.