450 Amp Wire Size at 200 Feet (12V DC (Solar / Automotive / Marine))
Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 450 A load over a 200 ft (61.0 m) one-way run.
Copper Wire (≤3% Drop)7× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.76%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 3.82V (31.85%)
Voltage at Load End11.7 VLoss: 0.33 V (149.0 W)
Power & Breaker (125%)5.4 kW600A Breaker Recommended
All AWG & kcmil Wire Gauges for 450 Amps at 200 Feet (12V)
| Wire Gauge | Metric Area | NEC 75°C Cu Ampacity | Copper Voltage Drop | Load Voltage | Aluminum Drop | Line Loss ($I^2R$) | NEC Status |
|---|---|---|---|---|---|---|---|
| 14 AWG | 2.08 mm² | 15 A | 564.47 V (4703.88%) | 0.0 V | 931.11 V (7759.21%) | 254009.8 W | Drop/Amp High |
| 12 AWG | 3.31 mm² | 20 A | 354.71 V (2955.92%) | 0.0 V | 585.11 V (4875.88%) | 159619.4 W | Drop/Amp High |
| 10 AWG | 5.26 mm² | 30 A | 223.21 V (1860.09%) | 0.0 V | 368.19 V (3068.28%) | 100444.9 W | Drop/Amp High |
| 8 AWG | 8.37 mm² | 50 A | 140.27 V (1168.95%) | 0.0 V | 231.39 V (1928.22%) | 63123.1 W | Drop/Amp High |
| 6 AWG | 13.3 mm² | 65 A | 88.28 V (735.65%) | 0.0 V | 145.62 V (1213.47%) | 39724.8 W | Drop/Amp High |
| 4 AWG | 21.15 mm² | 85 A | 55.51 V (462.6%) | 0.0 V | 91.57 V (763.08%) | 24980.6 W | Drop/Amp High |
| 3 AWG | 26.67 mm² | 100 A | 44.02 V (366.86%) | 0.0 V | 72.62 V (605.14%) | 19810.3 W | Drop/Amp High |
| 2 AWG | 33.62 mm² | 115 A | 34.92 V (291.02%) | 0.0 V | 57.61 V (480.05%) | 15715.1 W | Drop/Amp High |
| 1 AWG | 42.41 mm² | 130 A | 27.68 V (230.7%) | 0.0 V | 45.67 V (380.55%) | 12457.9 W | Drop/Amp High |
| 1/0 AWG | 53.49 mm² | 150 A | 21.95 V (182.91%) | 0.0 V | 36.21 V (301.72%) | 9877.4 W | Drop/Amp High |
| 2/0 AWG | 67.43 mm² | 175 A | 17.41 V (145.1%) | 0.0 V | 28.72 V (239.35%) | 7835.4 W | Drop/Amp High |
| 3/0 AWG | 85.01 mm² | 200 A | 13.81 V (115.09%) | 0.0 V | 22.78 V (189.85%) | 6215.0 W | Drop/Amp High |
| 4/0 AWG | 107.2 mm² | 230 A | 10.95 V (91.27%) | 1.0 V | 18.07 V (150.55%) | 4928.5 W | Drop/Amp High |
| 250 kcmil | 126.7 mm² | 255 A | 9.27 V (77.22%) | 2.7 V | 15.29 V (127.38%) | 4170.0 W | Drop/Amp High |
| 300 kcmil | 152.0 mm² | 285 A | 7.72 V (64.37%) | 4.3 V | 12.74 V (106.18%) | 3475.9 W | Drop/Amp High |
| 350 kcmil | 177.3 mm² | 310 A | 6.62 V (55.18%) | 5.4 V | 10.92 V (91.03%) | 2979.9 W | Drop/Amp High |
| 400 kcmil | 202.7 mm² | 335 A | 5.79 V (48.27%) | 6.2 V | 9.55 V (79.62%) | 2606.5 W | Drop/Amp High |
| 500 kcmil | 253.4 mm² | 380 A | 4.63 V (38.61%) | 7.4 V | 7.64 V (63.69%) | 2085.0 W | Drop/Amp High |
| 600 kcmil | 304.0 mm² | 420 A | 3.86 V (32.18%) | 8.1 V | 6.37 V (53.09%) | 1738.0 W | Drop/Amp High |
| 750 kcmil | 380.0 mm² | 475 A | 3.09 V (25.75%) | 8.9 V | 5.1 V (42.47%) | 1390.4 W | Drop/Amp High |
| 1000 kcmil | 506.7 mm² | 545 A | 2.32 V (19.31%) | 9.7 V | 3.82 V (31.85%) | 1042.7 W | Drop/Amp High |
Frequently Asked Engineering Questions
What size copper wire do I need for 450 amps at 200 feet (12V)?
To stay within the NEC recommended 3% maximum voltage drop for a 450A load over 200 feet one-way at 12V (DC), you need 7× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.33V (2.76%) and delivers 11.7V at the load.
What size aluminum wire is required for 450 amps at 200 feet?
Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 3.82V (31.85%).
What breaker size is needed for a 450A continuous load?
Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (450A × 1.25 = 562.5A), which corresponds to a standard 600A circuit breaker.
Compare Other Distances & Amperages
450 Amp Wire Size by Distance (12V)
450A at 20 ft (12V)450A at 30 ft (12V)450A at 40 ft (12V)450A at 50 ft (12V)450A at 60 ft (12V)450A at 75 ft (12V)450A at 80 ft (12V)450A at 100 ft (12V)450A at 120 ft (12V)450A at 125 ft (12V)450A at 150 ft (12V)450A at 175 ft (12V)