⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

5 Amp Wire Size at 30 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 5 A load over a 30 ft (9.1 m) one-way run.

Copper Wire (≤3% Drop)14 AWG2.08 mm² · Drop: 0.39%
Aluminum Wire (≤3% Drop)14 AWGDrop: 1.34V (0.65%)
Voltage at Load End207.2 VLoss: 0.81 V (7.1 W)
Power & Breaker (125%)1.8 kW10A Breaker Recommended

All AWG & kcmil Wire Gauges for 5 Amps at 30 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A0.81 V (0.39%)207.2 V1.34 V (0.65%)7.1 W✓ PASS (≤3%)
12 AWG3.31 mm²20 A0.51 V (0.25%)207.5 V0.84 V (0.41%)4.4 W✓ PASS (≤3%)
10 AWG5.26 mm²30 A0.32 V (0.15%)207.7 V0.53 V (0.26%)2.8 W✓ PASS (≤3%)
8 AWG8.37 mm²50 A0.2 V (0.1%)207.8 V0.33 V (0.16%)1.8 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A0.13 V (0.06%)207.9 V0.21 V (0.1%)1.1 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A0.08 V (0.04%)207.9 V0.13 V (0.06%)0.7 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.06 V (0.03%)207.9 V0.1 V (0.05%)0.6 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.05 V (0.02%)207.9 V0.08 V (0.04%)0.4 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.04 V (0.02%)208.0 V0.07 V (0.03%)0.3 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.03 V (0.02%)208.0 V0.05 V (0.03%)0.3 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.03 V (0.01%)208.0 V0.04 V (0.02%)0.2 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.02 V (0.01%)208.0 V0.03 V (0.02%)0.2 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.02 V (0.01%)208.0 V0.03 V (0.01%)0.1 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.01 V (0.01%)208.0 V0.02 V (0.01%)0.1 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.01 V (0.01%)208.0 V0.02 V (0.01%)0.1 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.01 V (0.0%)208.0 V0.02 V (0.01%)0.1 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.01 V (0.0%)208.0 V0.01 V (0.01%)0.1 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.01 V (0.0%)208.0 V0.01 V (0.01%)0.1 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.01 V (0.0%)208.0 V0.01 V (0.0%)0.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.0 V (0.0%)208.0 V0.01 V (0.0%)0.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.0 V (0.0%)208.0 V0.01 V (0.0%)0.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 5 amps at 30 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 5A load over 30 feet one-way at 208V (3-Phase), you need 14 AWG copper wire. This produces a voltage drop of 0.81V (0.39%) and delivers 207.2V at the load.

What size aluminum wire is required for 5 amps at 30 feet?

Using aluminum conductors (75°C rating), you should use 14 AWG to maintain voltage drop at 1.34V (0.65%).

What breaker size is needed for a 5A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (5A × 1.25 = 6.2A), which corresponds to a standard 10A circuit breaker.