⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

300 Amp Wire Size at 30 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 300 A load over a 30 ft (9.1 m) one-way run.

Copper Wire (≤3% Drop)350 kcmil177.3 mm² · Drop: 0.28%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 0.66V (0.32%)
Voltage at Load End207.4 VLoss: 0.57 V (298.0 W)
Power & Breaker (125%)108.08 kW400A Breaker Recommended

All AWG & kcmil Wire Gauges for 300 Amps at 30 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A48.88 V (23.5%)159.1 V80.64 V (38.77%)25401.0 WDrop/Amp High
12 AWG3.31 mm²20 A30.72 V (14.77%)177.3 V50.67 V (24.36%)15961.9 WDrop/Amp High
10 AWG5.26 mm²30 A19.33 V (9.29%)188.7 V31.89 V (15.33%)10044.5 WDrop/Amp High
8 AWG8.37 mm²50 A12.15 V (5.84%)195.9 V20.04 V (9.63%)6312.3 WDrop/Amp High
6 AWG13.3 mm²65 A7.65 V (3.68%)200.4 V12.61 V (6.06%)3972.5 WDrop/Amp High
4 AWG21.15 mm²85 A4.81 V (2.31%)203.2 V7.93 V (3.81%)2498.1 WDrop/Amp High
3 AWG26.67 mm²100 A3.81 V (1.83%)204.2 V6.29 V (3.02%)1981.0 WDrop/Amp High
2 AWG33.62 mm²115 A3.02 V (1.45%)205.0 V4.99 V (2.4%)1571.5 WDrop/Amp High
1 AWG42.41 mm²130 A2.4 V (1.15%)205.6 V3.95 V (1.9%)1245.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A1.9 V (0.91%)206.1 V3.14 V (1.51%)987.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A1.51 V (0.72%)206.5 V2.49 V (1.2%)783.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.2 V (0.58%)206.8 V1.97 V (0.95%)621.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A0.95 V (0.46%)207.1 V1.56 V (0.75%)492.9 WDrop/Amp High
250 kcmil126.7 mm²255 A0.8 V (0.39%)207.2 V1.32 V (0.64%)417.0 WDrop/Amp High
300 kcmil152.0 mm²285 A0.67 V (0.32%)207.3 V1.1 V (0.53%)347.6 WDrop/Amp High
350 kcmil177.3 mm²310 A0.57 V (0.28%)207.4 V0.95 V (0.45%)298.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.5 V (0.24%)207.5 V0.83 V (0.4%)260.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.4 V (0.19%)207.6 V0.66 V (0.32%)208.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.33 V (0.16%)207.7 V0.55 V (0.27%)173.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.27 V (0.13%)207.7 V0.44 V (0.21%)139.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.2 V (0.1%)207.8 V0.33 V (0.16%)104.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 300 amps at 30 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 300A load over 30 feet one-way at 208V (3-Phase), you need 350 kcmil copper wire. This produces a voltage drop of 0.57V (0.28%) and delivers 207.4V at the load.

What size aluminum wire is required for 300 amps at 30 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 0.66V (0.32%).

What breaker size is needed for a 300A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (300A × 1.25 = 375.0A), which corresponds to a standard 400A circuit breaker.