🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

50 Amp Wire Size at 50 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 50 A load over a 50 ft (15.2 m) one-way run.

Copper Wire (≤3% Drop)6 AWG13.3 mm² · Drop: 2.04%
Aluminum Wire (≤3% Drop)4 AWGDrop: 2.54V (2.12%)
Voltage at Load End117.5 VLoss: 2.45 V (122.6 W)
Power & Breaker (125%)6.0 kW63A Breaker Recommended

All AWG & kcmil Wire Gauges for 50 Amps at 50 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A15.68 V (13.07%)104.3 V25.86 V (21.55%)784.0 WDrop/Amp High
12 AWG3.31 mm²20 A9.85 V (8.21%)110.1 V16.25 V (13.54%)492.7 WDrop/Amp High
10 AWG5.26 mm²30 A6.2 V (5.17%)113.8 V10.23 V (8.52%)310.0 WDrop/Amp High
8 AWG8.37 mm²50 A3.9 V (3.25%)116.1 V6.43 V (5.36%)194.8 W~ ≤5%
6 AWG13.3 mm²65 A2.45 V (2.04%)117.5 V4.04 V (3.37%)122.6 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A1.54 V (1.29%)118.5 V2.54 V (2.12%)77.1 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.22 V (1.02%)118.8 V2.02 V (1.68%)61.1 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.97 V (0.81%)119.0 V1.6 V (1.33%)48.5 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.77 V (0.64%)119.2 V1.27 V (1.06%)38.5 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.61 V (0.51%)119.4 V1.01 V (0.84%)30.5 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.48 V (0.4%)119.5 V0.8 V (0.66%)24.2 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.38 V (0.32%)119.6 V0.63 V (0.53%)19.2 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.3 V (0.25%)119.7 V0.5 V (0.42%)15.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.26 V (0.21%)119.7 V0.42 V (0.35%)12.9 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.21 V (0.18%)119.8 V0.35 V (0.29%)10.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.18 V (0.15%)119.8 V0.3 V (0.25%)9.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.16 V (0.13%)119.8 V0.27 V (0.22%)8.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.13 V (0.11%)119.9 V0.21 V (0.18%)6.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.11 V (0.09%)119.9 V0.18 V (0.15%)5.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.09 V (0.07%)119.9 V0.14 V (0.12%)4.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.06 V (0.05%)119.9 V0.11 V (0.09%)3.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 50 amps at 50 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 50A load over 50 feet one-way at 120V (1-Phase), you need 6 AWG copper wire. This produces a voltage drop of 2.45V (2.04%) and delivers 117.5V at the load.

What size aluminum wire is required for 50 amps at 50 feet?

Using aluminum conductors (75°C rating), you should use 4 AWG to maintain voltage drop at 2.54V (2.12%).

What breaker size is needed for a 50A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (50A × 1.25 = 62.5A), which corresponds to a standard 63A circuit breaker.