⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

125 Amp Wire Size at 50 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 125 A load over a 50 ft (15.2 m) one-way run.

Copper Wire (≤3% Drop)1 AWG42.41 mm² · Drop: 1.6%
Aluminum Wire (≤3% Drop)2/0 AWGDrop: 1.99V (1.66%)
Voltage at Load End118.1 VLoss: 1.92 V (240.3 W)
Power & Breaker (125%)15.0 kW160A Breaker Recommended

All AWG & kcmil Wire Gauges for 125 Amps at 50 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A39.2 V (32.67%)80.8 V64.66 V (53.88%)4899.9 WDrop/Amp High
12 AWG3.31 mm²20 A24.63 V (20.53%)95.4 V40.63 V (33.86%)3079.1 WDrop/Amp High
10 AWG5.26 mm²30 A15.5 V (12.92%)104.5 V25.57 V (21.31%)1937.6 WDrop/Amp High
8 AWG8.37 mm²50 A9.74 V (8.12%)110.3 V16.07 V (13.39%)1217.7 WDrop/Amp High
6 AWG13.3 mm²65 A6.13 V (5.11%)113.9 V10.11 V (8.43%)766.3 WDrop/Amp High
4 AWG21.15 mm²85 A3.86 V (3.21%)116.1 V6.36 V (5.3%)481.9 WDrop/Amp High
3 AWG26.67 mm²100 A3.06 V (2.55%)116.9 V5.04 V (4.2%)382.1 WDrop/Amp High
2 AWG33.62 mm²115 A2.43 V (2.02%)117.6 V4.0 V (3.33%)303.1 WDrop/Amp High
1 AWG42.41 mm²130 A1.92 V (1.6%)118.1 V3.17 V (2.64%)240.3 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.52 V (1.27%)118.5 V2.51 V (2.1%)190.5 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.21 V (1.01%)118.8 V1.99 V (1.66%)151.1 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.96 V (0.8%)119.0 V1.58 V (1.32%)119.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.76 V (0.63%)119.2 V1.25 V (1.05%)95.1 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.64 V (0.54%)119.4 V1.06 V (0.88%)80.4 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.54 V (0.45%)119.5 V0.88 V (0.74%)67.1 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.46 V (0.38%)119.5 V0.76 V (0.63%)57.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.4 V (0.34%)119.6 V0.66 V (0.55%)50.3 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.32 V (0.27%)119.7 V0.53 V (0.44%)40.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.27 V (0.22%)119.7 V0.44 V (0.37%)33.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.21 V (0.18%)119.8 V0.35 V (0.29%)26.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.16 V (0.13%)119.8 V0.27 V (0.22%)20.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 125 amps at 50 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 125A load over 50 feet one-way at 120V (1-Phase), you need 1 AWG copper wire. This produces a voltage drop of 1.92V (1.6%) and delivers 118.1V at the load.

What size aluminum wire is required for 125 amps at 50 feet?

Using aluminum conductors (75°C rating), you should use 2/0 AWG to maintain voltage drop at 1.99V (1.66%).

What breaker size is needed for a 125A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (125A × 1.25 = 156.2A), which corresponds to a standard 160A circuit breaker.