🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

500 Amp Wire Size at 250 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 500 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)1000 kcmil506.7 mm² · Drop: 1.16%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 4.6V (1.92%)
Voltage at Load End237.2 VLoss: 2.79 V (2413.7 W)
Power & Breaker (125%)207.85 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 500 Amps at 250 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A678.95 V (282.89%)0.0 V1119.95 V (466.64%)587985.6 WDrop/Amp High
12 AWG3.31 mm²20 A426.65 V (177.77%)0.0 V703.77 V (293.24%)369489.4 WDrop/Amp High
10 AWG5.26 mm²30 A268.48 V (111.87%)0.0 V442.87 V (184.53%)232511.4 WDrop/Amp High
8 AWG8.37 mm²50 A168.72 V (70.3%)71.3 V278.31 V (115.96%)146118.3 WDrop/Amp High
6 AWG13.3 mm²65 A106.18 V (44.24%)133.8 V175.15 V (72.98%)91955.6 WDrop/Amp High
4 AWG21.15 mm²85 A66.77 V (27.82%)173.2 V110.14 V (45.89%)57825.5 WDrop/Amp High
3 AWG26.67 mm²100 A52.95 V (22.06%)187.0 V87.34 V (36.39%)45857.1 WDrop/Amp High
2 AWG33.62 mm²115 A42.01 V (17.5%)198.0 V69.29 V (28.87%)36377.5 WDrop/Amp High
1 AWG42.41 mm²130 A33.3 V (13.87%)206.7 V54.93 V (22.89%)28837.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A26.4 V (11.0%)213.6 V43.55 V (18.15%)22864.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A20.94 V (8.73%)219.1 V34.55 V (14.39%)18137.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A16.61 V (6.92%)223.4 V27.4 V (11.42%)14386.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A13.17 V (5.49%)226.8 V21.73 V (9.05%)11408.7 WDrop/Amp High
250 kcmil126.7 mm²255 A11.15 V (4.64%)228.9 V18.39 V (7.66%)9652.8 WDrop/Amp High
300 kcmil152.0 mm²285 A9.29 V (3.87%)230.7 V15.33 V (6.39%)8046.1 WDrop/Amp High
350 kcmil177.3 mm²310 A7.97 V (3.32%)232.0 V13.14 V (5.47%)6898.0 WDrop/Amp High
400 kcmil202.7 mm²335 A6.97 V (2.9%)233.0 V11.49 V (4.79%)6033.6 WDrop/Amp High
500 kcmil253.4 mm²380 A5.57 V (2.32%)234.4 V9.19 V (3.83%)4826.4 WDrop/Amp High
600 kcmil304.0 mm²420 A4.65 V (1.94%)235.4 V7.66 V (3.19%)4023.1 WDrop/Amp High
750 kcmil380.0 mm²475 A3.72 V (1.55%)236.3 V6.13 V (2.55%)3218.4 WDrop/Amp High
1000 kcmil506.7 mm²545 A2.79 V (1.16%)237.2 V4.6 V (1.92%)2413.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 500 amps at 250 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 500A load over 250 feet one-way at 240V (3-Phase), you need 1000 kcmil copper wire. This produces a voltage drop of 2.79V (1.16%) and delivers 237.2V at the load.

What size aluminum wire is required for 500 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 4.6V (1.92%).

What breaker size is needed for a 500A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (500A × 1.25 = 625.0A), which corresponds to a standard 700A circuit breaker.