🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

500 Amp Wire Size at 80 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 500 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)1000 kcmil506.7 mm² · Drop: 0.37%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.47V (0.61%)
Voltage at Load End239.1 VLoss: 0.89 V (772.4 W)
Power & Breaker (125%)207.85 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 500 Amps at 80 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A217.26 V (90.53%)22.7 V358.38 V (149.33%)188155.4 WDrop/Amp High
12 AWG3.31 mm²20 A136.53 V (56.89%)103.5 V225.21 V (93.84%)118236.6 WDrop/Amp High
10 AWG5.26 mm²30 A85.91 V (35.8%)154.1 V141.72 V (59.05%)74403.7 WDrop/Amp High
8 AWG8.37 mm²50 A53.99 V (22.5%)186.0 V89.06 V (37.11%)46757.8 WDrop/Amp High
6 AWG13.3 mm²65 A33.98 V (14.16%)206.0 V56.05 V (23.35%)29425.8 WDrop/Amp High
4 AWG21.15 mm²85 A21.37 V (8.9%)218.6 V35.25 V (14.69%)18504.2 WDrop/Amp High
3 AWG26.67 mm²100 A16.94 V (7.06%)223.1 V27.95 V (11.65%)14674.3 WDrop/Amp High
2 AWG33.62 mm²115 A13.44 V (5.6%)226.6 V22.17 V (9.24%)11640.8 WDrop/Amp High
1 AWG42.41 mm²130 A10.66 V (4.44%)229.3 V17.58 V (7.32%)9228.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A8.45 V (3.52%)231.6 V13.94 V (5.81%)7316.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A6.7 V (2.79%)233.3 V11.05 V (4.61%)5804.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A5.32 V (2.21%)234.7 V8.77 V (3.65%)4603.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A4.22 V (1.76%)235.8 V6.95 V (2.9%)3650.8 WDrop/Amp High
250 kcmil126.7 mm²255 A3.57 V (1.49%)236.4 V5.88 V (2.45%)3088.9 WDrop/Amp High
300 kcmil152.0 mm²285 A2.97 V (1.24%)237.0 V4.9 V (2.04%)2574.8 WDrop/Amp High
350 kcmil177.3 mm²310 A2.55 V (1.06%)237.5 V4.2 V (1.75%)2207.4 WDrop/Amp High
400 kcmil202.7 mm²335 A2.23 V (0.93%)237.8 V3.68 V (1.53%)1930.8 WDrop/Amp High
500 kcmil253.4 mm²380 A1.78 V (0.74%)238.2 V2.94 V (1.23%)1544.4 WDrop/Amp High
600 kcmil304.0 mm²420 A1.49 V (0.62%)238.5 V2.45 V (1.02%)1287.4 WDrop/Amp High
750 kcmil380.0 mm²475 A1.19 V (0.5%)238.8 V1.96 V (0.82%)1029.9 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.89 V (0.37%)239.1 V1.47 V (0.61%)772.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 500 amps at 80 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 500A load over 80 feet one-way at 240V (3-Phase), you need 1000 kcmil copper wire. This produces a voltage drop of 0.89V (0.37%) and delivers 239.1V at the load.

What size aluminum wire is required for 500 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.47V (0.61%).

What breaker size is needed for a 500A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (500A × 1.25 = 625.0A), which corresponds to a standard 700A circuit breaker.