🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

500 Amp Wire Size at 50 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 500 A load over a 50 ft (15.2 m) one-way run.

Copper Wire (≤3% Drop)1000 kcmil506.7 mm² · Drop: 0.27%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.92V (0.44%)
Voltage at Load End207.4 VLoss: 0.56 V (482.7 W)
Power & Breaker (125%)180.13 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 500 Amps at 50 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A135.79 V (65.28%)72.2 V223.99 V (107.69%)117597.1 WDrop/Amp High
12 AWG3.31 mm²20 A85.33 V (41.02%)122.7 V140.75 V (67.67%)73897.9 WDrop/Amp High
10 AWG5.26 mm²30 A53.7 V (25.82%)154.3 V88.57 V (42.58%)46502.3 WDrop/Amp High
8 AWG8.37 mm²50 A33.74 V (16.22%)174.3 V55.66 V (26.76%)29223.7 WDrop/Amp High
6 AWG13.3 mm²65 A21.24 V (10.21%)186.8 V35.03 V (16.84%)18391.1 WDrop/Amp High
4 AWG21.15 mm²85 A13.35 V (6.42%)194.6 V22.03 V (10.59%)11565.1 WDrop/Amp High
3 AWG26.67 mm²100 A10.59 V (5.09%)197.4 V17.47 V (8.4%)9171.4 WDrop/Amp High
2 AWG33.62 mm²115 A8.4 V (4.04%)199.6 V13.86 V (6.66%)7275.5 WDrop/Amp High
1 AWG42.41 mm²130 A6.66 V (3.2%)201.3 V10.99 V (5.28%)5767.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A5.28 V (2.54%)202.7 V8.71 V (4.19%)4572.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A4.19 V (2.01%)203.8 V6.91 V (3.32%)3627.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A3.32 V (1.6%)204.7 V5.48 V (2.63%)2877.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.63 V (1.27%)205.4 V4.35 V (2.09%)2281.7 WDrop/Amp High
250 kcmil126.7 mm²255 A2.23 V (1.07%)205.8 V3.68 V (1.77%)1930.6 WDrop/Amp High
300 kcmil152.0 mm²285 A1.86 V (0.89%)206.1 V3.07 V (1.47%)1609.2 WDrop/Amp High
350 kcmil177.3 mm²310 A1.59 V (0.77%)206.4 V2.63 V (1.26%)1379.6 WDrop/Amp High
400 kcmil202.7 mm²335 A1.39 V (0.67%)206.6 V2.3 V (1.11%)1206.7 WDrop/Amp High
500 kcmil253.4 mm²380 A1.11 V (0.54%)206.9 V1.84 V (0.88%)965.3 WDrop/Amp High
600 kcmil304.0 mm²420 A0.93 V (0.45%)207.1 V1.53 V (0.74%)804.6 WDrop/Amp High
750 kcmil380.0 mm²475 A0.74 V (0.36%)207.3 V1.23 V (0.59%)643.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.56 V (0.27%)207.4 V0.92 V (0.44%)482.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 500 amps at 50 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 500A load over 50 feet one-way at 208V (3-Phase), you need 1000 kcmil copper wire. This produces a voltage drop of 0.56V (0.27%) and delivers 207.4V at the load.

What size aluminum wire is required for 500 amps at 50 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.92V (0.44%).

What breaker size is needed for a 500A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (500A × 1.25 = 625.0A), which corresponds to a standard 700A circuit breaker.