500 Amp Wire Size at 750 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 500 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.01%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 13.79V (6.63%)
Voltage at Load End203.8 VLoss: 4.18 V (3620.5 W)
Power & Breaker (125%)180.13 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 500 Amps at 750 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2036.84 V (979.25%)0.0 V3359.84 V (1615.31%)1763956.7 WDrop/Amp High
12 AWG3.31 mm²20 A1279.95 V (615.36%)0.0 V2111.32 V (1015.06%)1108468.3 WDrop/Amp High
10 AWG5.26 mm²30 A805.44 V (387.23%)0.0 V1328.6 V (638.75%)697534.2 WDrop/Amp High
8 AWG8.37 mm²50 A506.17 V (243.35%)0.0 V834.94 V (401.41%)438354.8 WDrop/Amp High
6 AWG13.3 mm²65 A318.54 V (153.15%)0.0 V525.45 V (252.62%)275866.9 WDrop/Amp High
4 AWG21.15 mm²85 A200.31 V (96.3%)7.7 V330.42 V (158.86%)173476.6 WDrop/Amp High
3 AWG26.67 mm²100 A158.85 V (76.37%)49.1 V262.03 V (125.98%)137571.4 WDrop/Amp High
2 AWG33.62 mm²115 A126.02 V (60.58%)82.0 V207.87 V (99.94%)109132.4 WDrop/Amp High
1 AWG42.41 mm²130 A99.9 V (48.03%)108.1 V164.78 V (79.22%)86513.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A79.2 V (38.08%)128.8 V130.65 V (62.81%)68592.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A62.83 V (30.21%)145.2 V103.64 V (49.83%)54412.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A49.84 V (23.96%)158.2 V82.21 V (39.52%)43160.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A39.52 V (19.0%)168.5 V65.19 V (31.34%)34226.0 WDrop/Amp High
250 kcmil126.7 mm²255 A33.44 V (16.08%)174.6 V55.16 V (26.52%)28958.4 WDrop/Amp High
300 kcmil152.0 mm²285 A27.87 V (13.4%)180.1 V45.98 V (22.1%)24138.4 WDrop/Amp High
350 kcmil177.3 mm²310 A23.9 V (11.49%)184.1 V39.42 V (18.95%)20693.9 WDrop/Amp High
400 kcmil202.7 mm²335 A20.9 V (10.05%)187.1 V34.48 V (16.58%)18100.8 WDrop/Amp High
500 kcmil253.4 mm²380 A16.72 V (8.04%)191.3 V27.58 V (13.26%)14479.2 WDrop/Amp High
600 kcmil304.0 mm²420 A13.94 V (6.7%)194.1 V22.99 V (11.05%)12069.2 WDrop/Amp High
750 kcmil380.0 mm²475 A11.15 V (5.36%)196.9 V18.39 V (8.84%)9655.3 WDrop/Amp High
1000 kcmil506.7 mm²545 A8.36 V (4.02%)199.6 V13.79 V (6.63%)7241.0 W~ ≤5%

Frequently Asked Engineering Questions

What size copper wire do I need for 500 amps at 750 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 500A load over 750 feet one-way at 208V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 4.18V (2.01%) and delivers 203.8V at the load.

What size aluminum wire is required for 500 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 13.79V (6.63%).

What breaker size is needed for a 500A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (500A × 1.25 = 625.0A), which corresponds to a standard 700A circuit breaker.