🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

70 Amp Wire Size at 30 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 70 A load over a 30 ft (9.1 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 1.08%
Aluminum Wire (≤3% Drop)3 AWGDrop: 1.69V (1.41%)
Voltage at Load End118.7 VLoss: 1.3 V (90.7 W)
Power & Breaker (125%)8.4 kW90A Breaker Recommended

All AWG & kcmil Wire Gauges for 70 Amps at 30 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A13.17 V (10.98%)106.8 V21.73 V (18.1%)922.0 WDrop/Amp High
12 AWG3.31 mm²20 A8.28 V (6.9%)111.7 V13.65 V (11.38%)579.4 WDrop/Amp High
10 AWG5.26 mm²30 A5.21 V (4.34%)114.8 V8.59 V (7.16%)364.6 WDrop/Amp High
8 AWG8.37 mm²50 A3.27 V (2.73%)116.7 V5.4 V (4.5%)229.1 WDrop/Amp High
6 AWG13.3 mm²65 A2.06 V (1.72%)117.9 V3.4 V (2.83%)144.2 WDrop/Amp High
4 AWG21.15 mm²85 A1.3 V (1.08%)118.7 V2.14 V (1.78%)90.7 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.03 V (0.86%)119.0 V1.69 V (1.41%)71.9 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.81 V (0.68%)119.2 V1.34 V (1.12%)57.0 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.65 V (0.54%)119.4 V1.07 V (0.89%)45.2 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.51 V (0.43%)119.5 V0.84 V (0.7%)35.9 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.41 V (0.34%)119.6 V0.67 V (0.56%)28.4 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.32 V (0.27%)119.7 V0.53 V (0.44%)22.6 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.26 V (0.21%)119.7 V0.42 V (0.35%)17.9 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.22 V (0.18%)119.8 V0.36 V (0.3%)15.1 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.18 V (0.15%)119.8 V0.3 V (0.25%)12.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.15 V (0.13%)119.8 V0.25 V (0.21%)10.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.14 V (0.11%)119.9 V0.22 V (0.19%)9.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.11 V (0.09%)119.9 V0.18 V (0.15%)7.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.09 V (0.08%)119.9 V0.15 V (0.12%)6.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.07 V (0.06%)119.9 V0.12 V (0.1%)5.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.05 V (0.05%)119.9 V0.09 V (0.07%)3.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 70 amps at 30 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 70A load over 30 feet one-way at 120V (1-Phase), you need 4 AWG copper wire. This produces a voltage drop of 1.3V (1.08%) and delivers 118.7V at the load.

What size aluminum wire is required for 70 amps at 30 feet?

Using aluminum conductors (75°C rating), you should use 3 AWG to maintain voltage drop at 1.69V (1.41%).

What breaker size is needed for a 70A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (70A × 1.25 = 87.5A), which corresponds to a standard 90A circuit breaker.