⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

70 Amp Wire Size at 150 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 70 A load over a 150 ft (45.7 m) one-way run.

Copper Wire (≤3% Drop)1 AWG42.41 mm² · Drop: 2.69%
Aluminum Wire (≤3% Drop)2/0 AWGDrop: 3.35V (2.79%)
Voltage at Load End116.8 VLoss: 3.23 V (226.1 W)
Power & Breaker (125%)8.4 kW90A Breaker Recommended

All AWG & kcmil Wire Gauges for 70 Amps at 150 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A65.85 V (54.88%)54.1 V108.63 V (90.52%)4609.8 WDrop/Amp High
12 AWG3.31 mm²20 A41.38 V (34.49%)78.6 V68.26 V (56.89%)2896.8 WDrop/Amp High
10 AWG5.26 mm²30 A26.04 V (21.7%)94.0 V42.96 V (35.8%)1822.9 WDrop/Amp High
8 AWG8.37 mm²50 A16.37 V (13.64%)103.6 V27.0 V (22.5%)1145.6 WDrop/Amp High
6 AWG13.3 mm²65 A10.3 V (8.58%)109.7 V16.99 V (14.16%)720.9 WDrop/Amp High
4 AWG21.15 mm²85 A6.48 V (5.4%)113.5 V10.68 V (8.9%)453.4 WDrop/Amp High
3 AWG26.67 mm²100 A5.14 V (4.28%)114.9 V8.47 V (7.06%)359.5 W~ ≤5%
2 AWG33.62 mm²115 A4.07 V (3.4%)115.9 V6.72 V (5.6%)285.2 W~ ≤5%
1 AWG42.41 mm²130 A3.23 V (2.69%)116.8 V5.33 V (4.44%)226.1 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A2.56 V (2.13%)117.4 V4.22 V (3.52%)179.3 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A2.03 V (1.69%)118.0 V3.35 V (2.79%)142.2 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.61 V (1.34%)118.4 V2.66 V (2.21%)112.8 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.28 V (1.06%)118.7 V2.11 V (1.76%)89.4 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.08 V (0.9%)118.9 V1.78 V (1.49%)75.7 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.9 V (0.75%)119.1 V1.49 V (1.24%)63.1 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.77 V (0.64%)119.2 V1.27 V (1.06%)54.1 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.68 V (0.56%)119.3 V1.11 V (0.93%)47.3 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.54 V (0.45%)119.5 V0.89 V (0.74%)37.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.45 V (0.38%)119.5 V0.74 V (0.62%)31.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.36 V (0.3%)119.6 V0.59 V (0.5%)25.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.27 V (0.23%)119.7 V0.45 V (0.37%)18.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 70 amps at 150 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 70A load over 150 feet one-way at 120V (1-Phase), you need 1 AWG copper wire. This produces a voltage drop of 3.23V (2.69%) and delivers 116.8V at the load.

What size aluminum wire is required for 70 amps at 150 feet?

Using aluminum conductors (75°C rating), you should use 2/0 AWG to maintain voltage drop at 3.35V (2.79%).

What breaker size is needed for a 70A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (70A × 1.25 = 87.5A), which corresponds to a standard 90A circuit breaker.