700 Amp Wire Size at 175 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.66%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 4.51V (2.17%)
Voltage at Load End206.6 VLoss: 1.36 V (1655.8 W)
Power & Breaker (125%)252.19 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 175 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A665.37 V (319.89%)0.0 V1097.55 V (527.67%)806716.2 WDrop/Amp High
12 AWG3.31 mm²20 A418.12 V (201.02%)0.0 V689.7 V (331.59%)506939.5 WDrop/Amp High
10 AWG5.26 mm²30 A263.11 V (126.5%)0.0 V434.01 V (208.66%)319005.7 WDrop/Amp High
8 AWG8.37 mm²50 A165.35 V (79.49%)42.7 V272.75 V (131.13%)200474.3 WDrop/Amp High
6 AWG13.3 mm²65 A104.06 V (50.03%)103.9 V171.65 V (82.52%)126163.1 WDrop/Amp High
4 AWG21.15 mm²85 A65.44 V (31.46%)142.6 V107.94 V (51.89%)79336.6 WDrop/Amp High
3 AWG26.67 mm²100 A51.89 V (24.95%)156.1 V85.6 V (41.15%)62916.0 WDrop/Amp High
2 AWG33.62 mm²115 A41.16 V (19.79%)166.8 V67.9 V (32.65%)49909.9 WDrop/Amp High
1 AWG42.41 mm²130 A32.63 V (15.69%)175.4 V53.83 V (25.88%)39565.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A25.87 V (12.44%)182.1 V42.68 V (20.52%)31369.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A20.52 V (9.87%)187.5 V33.86 V (16.28%)24884.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A16.28 V (7.83%)191.7 V26.85 V (12.91%)19738.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A12.91 V (6.21%)195.1 V21.3 V (10.24%)15652.7 WDrop/Amp High
250 kcmil126.7 mm²255 A10.92 V (5.25%)197.1 V18.02 V (8.66%)13243.6 WDrop/Amp High
300 kcmil152.0 mm²285 A9.11 V (4.38%)198.9 V15.02 V (7.22%)11039.3 WDrop/Amp High
350 kcmil177.3 mm²310 A7.81 V (3.75%)200.2 V12.88 V (6.19%)9464.0 WDrop/Amp High
400 kcmil202.7 mm²335 A6.83 V (3.28%)201.2 V11.26 V (5.41%)8278.1 WDrop/Amp High
500 kcmil253.4 mm²380 A5.46 V (2.63%)202.5 V9.01 V (4.33%)6621.8 WDrop/Amp High
600 kcmil304.0 mm²420 A4.55 V (2.19%)203.4 V7.51 V (3.61%)5519.6 WDrop/Amp High
750 kcmil380.0 mm²475 A3.64 V (1.75%)204.4 V6.01 V (2.89%)4415.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A2.73 V (1.31%)205.3 V4.51 V (2.17%)3311.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 175 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 175 feet one-way at 208V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.36V (0.66%) and delivers 206.6V at the load.

What size aluminum wire is required for 700 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 4.51V (2.17%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.