⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 600 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.25%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 15.45V (7.43%)
Voltage at Load End203.3 VLoss: 4.68 V (5676.9 W)
Power & Breaker (125%)252.19 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 600 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2281.26 V (1096.76%)0.0 V3763.02 V (1809.14%)2765884.2 WDrop/Amp High
12 AWG3.31 mm²20 A1433.54 V (689.2%)0.0 V2364.68 V (1136.86%)1738078.3 WDrop/Amp High
10 AWG5.26 mm²30 A902.1 V (433.7%)0.0 V1488.04 V (715.4%)1093733.7 WDrop/Amp High
8 AWG8.37 mm²50 A566.91 V (272.55%)0.0 V935.13 V (449.58%)687340.4 WDrop/Amp High
6 AWG13.3 mm²65 A356.77 V (171.52%)0.0 V588.5 V (282.93%)432559.3 WDrop/Amp High
4 AWG21.15 mm²85 A224.35 V (107.86%)0.0 V370.07 V (177.92%)272011.3 WDrop/Amp High
3 AWG26.67 mm²100 A177.92 V (85.54%)30.1 V293.48 V (141.1%)215712.0 WDrop/Amp High
2 AWG33.62 mm²115 A141.14 V (67.85%)66.9 V232.81 V (111.93%)171119.5 WDrop/Amp High
1 AWG42.41 mm²130 A111.88 V (53.79%)96.1 V184.56 V (88.73%)135652.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A88.71 V (42.65%)119.3 V146.33 V (70.35%)107553.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A70.37 V (33.83%)137.6 V116.08 V (55.81%)85318.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A55.82 V (26.84%)152.2 V92.07 V (44.27%)67674.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A44.26 V (21.28%)163.7 V73.01 V (35.1%)53666.4 WDrop/Amp High
250 kcmil126.7 mm²255 A37.45 V (18.01%)170.5 V61.78 V (29.7%)45406.8 WDrop/Amp High
300 kcmil152.0 mm²285 A31.22 V (15.01%)176.8 V51.49 V (24.76%)37848.9 WDrop/Amp High
350 kcmil177.3 mm²310 A26.76 V (12.87%)181.2 V44.15 V (21.22%)32448.0 WDrop/Amp High
400 kcmil202.7 mm²335 A23.41 V (11.25%)184.6 V38.61 V (18.56%)28382.0 WDrop/Amp High
500 kcmil253.4 mm²380 A18.73 V (9.0%)189.3 V30.89 V (14.85%)22703.4 WDrop/Amp High
600 kcmil304.0 mm²420 A15.61 V (7.5%)192.4 V25.75 V (12.38%)18924.5 WDrop/Amp High
750 kcmil380.0 mm²475 A12.49 V (6.0%)195.5 V20.6 V (9.9%)15139.6 WDrop/Amp High
1000 kcmil506.7 mm²545 A9.36 V (4.5%)198.6 V15.45 V (7.43%)11353.9 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 600 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 600 feet one-way at 208V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 4.68V (2.25%) and delivers 203.3V at the load.

What size aluminum wire is required for 700 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 15.45V (7.43%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.