🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 750 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.81%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 19.31V (9.28%)
Voltage at Load End202.1 VLoss: 5.86 V (7096.2 W)
Power & Breaker (125%)252.19 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 750 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2851.58 V (1370.95%)0.0 V4703.77 V (2261.43%)3457355.2 WDrop/Amp High
12 AWG3.31 mm²20 A1791.93 V (861.5%)0.0 V2955.84 V (1421.08%)2172597.8 WDrop/Amp High
10 AWG5.26 mm²30 A1127.62 V (542.13%)0.0 V1860.05 V (894.25%)1367167.1 WDrop/Amp High
8 AWG8.37 mm²50 A708.64 V (340.69%)0.0 V1168.92 V (561.98%)859175.5 WDrop/Amp High
6 AWG13.3 mm²65 A445.96 V (214.4%)0.0 V735.63 V (353.67%)540699.2 WDrop/Amp High
4 AWG21.15 mm²85 A280.44 V (134.83%)0.0 V462.59 V (222.4%)340014.1 WDrop/Amp High
3 AWG26.67 mm²100 A222.4 V (106.92%)0.0 V366.85 V (176.37%)269640.0 WDrop/Amp High
2 AWG33.62 mm²115 A176.42 V (84.82%)31.6 V291.01 V (139.91%)213899.4 WDrop/Amp High
1 AWG42.41 mm²130 A139.86 V (67.24%)68.1 V230.7 V (110.91%)169566.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A110.89 V (53.31%)97.1 V182.91 V (87.94%)134441.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A87.96 V (42.29%)120.0 V145.1 V (69.76%)106648.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A69.77 V (33.54%)138.2 V115.09 V (55.33%)84593.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A55.33 V (26.6%)152.7 V91.27 V (43.88%)67083.0 WDrop/Amp High
250 kcmil126.7 mm²255 A46.81 V (22.51%)161.2 V77.22 V (37.13%)56758.5 WDrop/Amp High
300 kcmil152.0 mm²285 A39.02 V (18.76%)169.0 V64.37 V (30.95%)47311.2 WDrop/Amp High
350 kcmil177.3 mm²310 A33.45 V (16.08%)174.5 V55.18 V (26.53%)40560.1 WDrop/Amp High
400 kcmil202.7 mm²335 A29.26 V (14.07%)178.7 V48.27 V (23.21%)35477.5 WDrop/Amp High
500 kcmil253.4 mm²380 A23.41 V (11.25%)184.6 V38.61 V (18.56%)28379.2 WDrop/Amp High
600 kcmil304.0 mm²420 A19.51 V (9.38%)188.5 V32.18 V (15.47%)23655.6 WDrop/Amp High
750 kcmil380.0 mm²475 A15.61 V (7.5%)192.4 V25.75 V (12.38%)18924.5 WDrop/Amp High
1000 kcmil506.7 mm²545 A11.71 V (5.63%)196.3 V19.31 V (9.28%)14192.4 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 750 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 750 feet one-way at 208V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 5.86V (2.81%) and delivers 202.1V at the load.

What size aluminum wire is required for 700 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 19.31V (9.28%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.