🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

750 Amp Wire Size at 250 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 750 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.0%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 6.9V (3.32%)
Voltage at Load End205.9 VLoss: 2.09 V (2715.4 W)
Power & Breaker (125%)270.2 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 750 Amps at 250 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1018.42 V (489.63%)0.0 V1679.92 V (807.65%)1322967.5 WDrop/Amp High
12 AWG3.31 mm²20 A639.97 V (307.68%)0.0 V1055.66 V (507.53%)831351.2 WDrop/Amp High
10 AWG5.26 mm²30 A402.72 V (193.62%)0.0 V664.3 V (319.38%)523150.7 WDrop/Amp High
8 AWG8.37 mm²50 A253.08 V (121.68%)0.0 V417.47 V (200.71%)328766.1 WDrop/Amp High
6 AWG13.3 mm²65 A159.27 V (76.57%)48.7 V262.72 V (126.31%)206900.2 WDrop/Amp High
4 AWG21.15 mm²85 A100.16 V (48.15%)107.8 V165.21 V (79.43%)130107.4 WDrop/Amp High
3 AWG26.67 mm²100 A79.43 V (38.19%)128.6 V131.02 V (62.99%)103178.6 WDrop/Amp High
2 AWG33.62 mm²115 A63.01 V (30.29%)145.0 V103.93 V (49.97%)81849.3 WDrop/Amp High
1 AWG42.41 mm²130 A49.95 V (24.01%)158.1 V82.39 V (39.61%)64885.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A39.6 V (19.04%)168.4 V65.32 V (31.41%)51444.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A31.42 V (15.1%)176.6 V51.82 V (24.91%)40809.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A24.92 V (11.98%)183.1 V41.1 V (19.76%)32370.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A19.76 V (9.5%)188.2 V32.6 V (15.67%)25669.5 WDrop/Amp High
250 kcmil126.7 mm²255 A16.72 V (8.04%)191.3 V27.58 V (13.26%)21718.8 WDrop/Amp High
300 kcmil152.0 mm²285 A13.94 V (6.7%)194.1 V22.99 V (11.05%)18103.8 WDrop/Amp High
350 kcmil177.3 mm²310 A11.95 V (5.74%)196.1 V19.71 V (9.48%)15520.4 WDrop/Amp High
400 kcmil202.7 mm²335 A10.45 V (5.02%)197.5 V17.24 V (8.29%)13575.6 WDrop/Amp High
500 kcmil253.4 mm²380 A8.36 V (4.02%)199.6 V13.79 V (6.63%)10859.4 WDrop/Amp High
600 kcmil304.0 mm²420 A6.97 V (3.35%)201.0 V11.49 V (5.53%)9051.9 WDrop/Amp High
750 kcmil380.0 mm²475 A5.57 V (2.68%)202.4 V9.2 V (4.42%)7241.5 WDrop/Amp High
1000 kcmil506.7 mm²545 A4.18 V (2.01%)203.8 V6.9 V (3.32%)5430.8 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 750 amps at 250 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 750A load over 250 feet one-way at 208V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.09V (1.0%) and delivers 205.9V at the load.

What size aluminum wire is required for 750 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 6.9V (3.32%).

What breaker size is needed for a 750A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (750A × 1.25 = 937.5A), which corresponds to a standard 1000A circuit breaker.