🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

80 Amp Wire Size at 40 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 80 A load over a 40 ft (12.2 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 0.71%
Aluminum Wire (≤3% Drop)2 AWGDrop: 1.77V (0.74%)
Voltage at Load End238.3 VLoss: 1.71 V (236.9 W)
Power & Breaker (125%)33.26 kW100A Breaker Recommended

All AWG & kcmil Wire Gauges for 80 Amps at 40 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A17.38 V (7.24%)222.6 V28.67 V (11.95%)2408.4 WDrop/Amp High
12 AWG3.31 mm²20 A10.92 V (4.55%)229.1 V18.02 V (7.51%)1513.4 WDrop/Amp High
10 AWG5.26 mm²30 A6.87 V (2.86%)233.1 V11.34 V (4.72%)952.4 WDrop/Amp High
8 AWG8.37 mm²50 A4.32 V (1.8%)235.7 V7.12 V (2.97%)598.5 WDrop/Amp High
6 AWG13.3 mm²65 A2.72 V (1.13%)237.3 V4.48 V (1.87%)376.7 WDrop/Amp High
4 AWG21.15 mm²85 A1.71 V (0.71%)238.3 V2.82 V (1.17%)236.9 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.36 V (0.56%)238.6 V2.24 V (0.93%)187.8 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.08 V (0.45%)238.9 V1.77 V (0.74%)149.0 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.85 V (0.36%)239.1 V1.41 V (0.59%)118.1 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.68 V (0.28%)239.3 V1.11 V (0.46%)93.7 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.54 V (0.22%)239.5 V0.88 V (0.37%)74.3 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.43 V (0.18%)239.6 V0.7 V (0.29%)58.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.34 V (0.14%)239.7 V0.56 V (0.23%)46.7 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.29 V (0.12%)239.7 V0.47 V (0.2%)39.5 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.24 V (0.1%)239.8 V0.39 V (0.16%)33.0 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.2 V (0.08%)239.8 V0.34 V (0.14%)28.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.18 V (0.07%)239.8 V0.29 V (0.12%)24.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.14 V (0.06%)239.9 V0.24 V (0.1%)19.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.12 V (0.05%)239.9 V0.2 V (0.08%)16.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.1 V (0.04%)239.9 V0.16 V (0.07%)13.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.07 V (0.03%)239.9 V0.12 V (0.05%)9.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 80 amps at 40 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 80A load over 40 feet one-way at 240V (3-Phase), you need 4 AWG copper wire. This produces a voltage drop of 1.71V (0.71%) and delivers 238.3V at the load.

What size aluminum wire is required for 80 amps at 40 feet?

Using aluminum conductors (75°C rating), you should use 2 AWG to maintain voltage drop at 1.77V (0.74%).

What breaker size is needed for a 80A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (80A × 1.25 = 100.0A), which corresponds to a standard 100A circuit breaker.