⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

80 Amp Wire Size at 120 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 80 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 2.14%
Aluminum Wire (≤3% Drop)2 AWGDrop: 5.32V (2.22%)
Voltage at Load End234.9 VLoss: 5.13 V (710.6 W)
Power & Breaker (125%)33.26 kW100A Breaker Recommended

All AWG & kcmil Wire Gauges for 80 Amps at 120 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A52.14 V (21.73%)187.9 V86.01 V (35.84%)7225.2 WDrop/Amp High
12 AWG3.31 mm²20 A32.77 V (13.65%)207.2 V54.05 V (22.52%)4540.3 WDrop/Amp High
10 AWG5.26 mm²30 A20.62 V (8.59%)219.4 V34.01 V (14.17%)2857.1 WDrop/Amp High
8 AWG8.37 mm²50 A12.96 V (5.4%)227.0 V21.37 V (8.91%)1795.5 WDrop/Amp High
6 AWG13.3 mm²65 A8.15 V (3.4%)231.8 V13.45 V (5.6%)1130.0 WDrop/Amp High
4 AWG21.15 mm²85 A5.13 V (2.14%)234.9 V8.46 V (3.52%)710.6 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A4.07 V (1.69%)235.9 V6.71 V (2.8%)563.5 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A3.23 V (1.34%)236.8 V5.32 V (2.22%)447.0 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A2.56 V (1.07%)237.4 V4.22 V (1.76%)354.4 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A2.03 V (0.84%)238.0 V3.34 V (1.39%)281.0 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.61 V (0.67%)238.4 V2.65 V (1.11%)222.9 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.28 V (0.53%)238.7 V2.1 V (0.88%)176.8 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.01 V (0.42%)239.0 V1.67 V (0.7%)140.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.86 V (0.36%)239.1 V1.41 V (0.59%)118.6 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.71 V (0.3%)239.3 V1.18 V (0.49%)98.9 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.61 V (0.25%)239.4 V1.01 V (0.42%)84.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.54 V (0.22%)239.5 V0.88 V (0.37%)74.1 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.43 V (0.18%)239.6 V0.71 V (0.29%)59.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.36 V (0.15%)239.6 V0.59 V (0.25%)49.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.29 V (0.12%)239.7 V0.47 V (0.2%)39.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.21 V (0.09%)239.8 V0.35 V (0.15%)29.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 80 amps at 120 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 80A load over 120 feet one-way at 240V (3-Phase), you need 4 AWG copper wire. This produces a voltage drop of 5.13V (2.14%) and delivers 234.9V at the load.

What size aluminum wire is required for 80 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 2 AWG to maintain voltage drop at 5.32V (2.22%).

What breaker size is needed for a 80A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (80A × 1.25 = 100.0A), which corresponds to a standard 100A circuit breaker.