🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

80 Amp Wire Size at 450 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 80 A load over a 450 ft (137.2 m) one-way run.

Copper Wire (≤3% Drop)2/0 AWG67.43 mm² · Drop: 2.9%
Aluminum Wire (≤3% Drop)250 kcmilDrop: 5.3V (2.55%)
Voltage at Load End202.0 VLoss: 6.03 V (835.8 W)
Power & Breaker (125%)28.82 kW100A Breaker Recommended

All AWG & kcmil Wire Gauges for 80 Amps at 450 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A195.54 V (94.01%)12.5 V322.54 V (155.07%)27094.4 WDrop/Amp High
12 AWG3.31 mm²20 A122.88 V (59.07%)85.1 V202.69 V (97.45%)17026.1 WDrop/Amp High
10 AWG5.26 mm²30 A77.32 V (37.17%)130.7 V127.55 V (61.32%)10714.1 WDrop/Amp High
8 AWG8.37 mm²50 A48.59 V (23.36%)159.4 V80.15 V (38.54%)6733.1 WDrop/Amp High
6 AWG13.3 mm²65 A30.58 V (14.7%)177.4 V50.44 V (24.25%)4237.3 WDrop/Amp High
4 AWG21.15 mm²85 A19.23 V (9.25%)188.8 V31.72 V (15.25%)2664.6 WDrop/Amp High
3 AWG26.67 mm²100 A15.25 V (7.33%)192.8 V25.16 V (12.09%)2113.1 WDrop/Amp High
2 AWG33.62 mm²115 A12.1 V (5.82%)195.9 V19.96 V (9.59%)1676.3 WDrop/Amp High
1 AWG42.41 mm²130 A9.59 V (4.61%)198.4 V15.82 V (7.61%)1328.8 W~ ≤5%
1/0 AWG53.49 mm²150 A7.6 V (3.66%)200.4 V12.54 V (6.03%)1053.6 W~ ≤5%
2/0 AWG67.43 mm²175 A6.03 V (2.9%)202.0 V9.95 V (4.78%)835.8 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A4.78 V (2.3%)203.2 V7.89 V (3.79%)662.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A3.79 V (1.82%)204.2 V6.26 V (3.01%)525.7 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A3.21 V (1.54%)204.8 V5.3 V (2.55%)444.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.68 V (1.29%)205.3 V4.41 V (2.12%)370.8 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.29 V (1.1%)205.7 V3.78 V (1.82%)317.9 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.01 V (0.96%)206.0 V3.31 V (1.59%)278.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.61 V (0.77%)206.4 V2.65 V (1.27%)222.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.34 V (0.64%)206.7 V2.21 V (1.06%)185.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.07 V (0.51%)206.9 V1.77 V (0.85%)148.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.8 V (0.39%)207.2 V1.32 V (0.64%)111.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 80 amps at 450 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 80A load over 450 feet one-way at 208V (3-Phase), you need 2/0 AWG copper wire. This produces a voltage drop of 6.03V (2.9%) and delivers 202.0V at the load.

What size aluminum wire is required for 80 amps at 450 feet?

Using aluminum conductors (75°C rating), you should use 250 kcmil to maintain voltage drop at 5.3V (2.55%).

What breaker size is needed for a 80A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (80A × 1.25 = 100.0A), which corresponds to a standard 100A circuit breaker.