🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

80 Amp Wire Size at 120 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 80 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 2.47%
Aluminum Wire (≤3% Drop)2 AWGDrop: 5.32V (2.56%)
Voltage at Load End202.9 VLoss: 5.13 V (710.6 W)
Power & Breaker (125%)28.82 kW100A Breaker Recommended

All AWG & kcmil Wire Gauges for 80 Amps at 120 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A52.14 V (25.07%)155.9 V86.01 V (41.35%)7225.2 WDrop/Amp High
12 AWG3.31 mm²20 A32.77 V (15.75%)175.2 V54.05 V (25.99%)4540.3 WDrop/Amp High
10 AWG5.26 mm²30 A20.62 V (9.91%)187.4 V34.01 V (16.35%)2857.1 WDrop/Amp High
8 AWG8.37 mm²50 A12.96 V (6.23%)195.0 V21.37 V (10.28%)1795.5 WDrop/Amp High
6 AWG13.3 mm²65 A8.15 V (3.92%)199.8 V13.45 V (6.47%)1130.0 WDrop/Amp High
4 AWG21.15 mm²85 A5.13 V (2.47%)202.9 V8.46 V (4.07%)710.6 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A4.07 V (1.96%)203.9 V6.71 V (3.23%)563.5 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A3.23 V (1.55%)204.8 V5.32 V (2.56%)447.0 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A2.56 V (1.23%)205.4 V4.22 V (2.03%)354.4 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A2.03 V (0.97%)206.0 V3.34 V (1.61%)281.0 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.61 V (0.77%)206.4 V2.65 V (1.28%)222.9 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.28 V (0.61%)206.7 V2.1 V (1.01%)176.8 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.01 V (0.49%)207.0 V1.67 V (0.8%)140.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.86 V (0.41%)207.1 V1.41 V (0.68%)118.6 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.71 V (0.34%)207.3 V1.18 V (0.57%)98.9 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.61 V (0.29%)207.4 V1.01 V (0.49%)84.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.54 V (0.26%)207.5 V0.88 V (0.42%)74.1 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.43 V (0.21%)207.6 V0.71 V (0.34%)59.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.36 V (0.17%)207.6 V0.59 V (0.28%)49.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.29 V (0.14%)207.7 V0.47 V (0.23%)39.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.21 V (0.1%)207.8 V0.35 V (0.17%)29.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 80 amps at 120 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 80A load over 120 feet one-way at 208V (3-Phase), you need 4 AWG copper wire. This produces a voltage drop of 5.13V (2.47%) and delivers 202.9V at the load.

What size aluminum wire is required for 80 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 2 AWG to maintain voltage drop at 5.32V (2.56%).

What breaker size is needed for a 80A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (80A × 1.25 = 100.0A), which corresponds to a standard 100A circuit breaker.