🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

800 Amp Wire Size at 125 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 800 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.47%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 3.68V (1.53%)
Voltage at Load End238.9 VLoss: 1.11 V (1544.8 W)
Power & Breaker (125%)332.55 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 800 Amps at 125 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A543.16 V (226.32%)0.0 V895.96 V (373.32%)752621.5 WDrop/Amp High
12 AWG3.31 mm²20 A341.32 V (142.22%)0.0 V563.02 V (234.59%)472946.5 WDrop/Amp High
10 AWG5.26 mm²30 A214.78 V (89.49%)25.2 V354.29 V (147.62%)297614.6 WDrop/Amp High
8 AWG8.37 mm²50 A134.98 V (56.24%)105.0 V222.65 V (92.77%)187031.4 WDrop/Amp High
6 AWG13.3 mm²65 A84.94 V (35.39%)155.1 V140.12 V (58.38%)117703.2 WDrop/Amp High
4 AWG21.15 mm²85 A53.42 V (22.26%)186.6 V88.11 V (36.71%)74016.7 WDrop/Amp High
3 AWG26.67 mm²100 A42.36 V (17.65%)197.6 V69.88 V (29.11%)58697.1 WDrop/Amp High
2 AWG33.62 mm²115 A33.6 V (14.0%)206.4 V55.43 V (23.1%)46563.1 WDrop/Amp High
1 AWG42.41 mm²130 A26.64 V (11.1%)213.4 V43.94 V (18.31%)36912.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A21.12 V (8.8%)218.9 V34.84 V (14.52%)29266.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A16.75 V (6.98%)223.2 V27.64 V (11.52%)23216.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A13.29 V (5.54%)226.7 V21.92 V (9.13%)18414.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A10.54 V (4.39%)229.5 V17.38 V (7.24%)14603.1 WDrop/Amp High
250 kcmil126.7 mm²255 A8.92 V (3.72%)231.1 V14.71 V (6.13%)12355.6 WDrop/Amp High
300 kcmil152.0 mm²285 A7.43 V (3.1%)232.6 V12.26 V (5.11%)10299.0 WDrop/Amp High
350 kcmil177.3 mm²310 A6.37 V (2.66%)233.6 V10.51 V (4.38%)8829.4 WDrop/Amp High
400 kcmil202.7 mm²335 A5.57 V (2.32%)234.4 V9.19 V (3.83%)7723.0 WDrop/Amp High
500 kcmil253.4 mm²380 A4.46 V (1.86%)235.5 V7.35 V (3.06%)6177.8 WDrop/Amp High
600 kcmil304.0 mm²420 A3.72 V (1.55%)236.3 V6.13 V (2.55%)5149.5 WDrop/Amp High
750 kcmil380.0 mm²475 A2.97 V (1.24%)237.0 V4.9 V (2.04%)4119.6 WDrop/Amp High
1000 kcmil506.7 mm²545 A2.23 V (0.93%)237.8 V3.68 V (1.53%)3089.5 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 800 amps at 125 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 800A load over 125 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.11V (0.47%) and delivers 238.9V at the load.

What size aluminum wire is required for 800 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 3.68V (1.53%).

What breaker size is needed for a 800A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (800A × 1.25 = 1000.0A), which corresponds to a standard 1000A circuit breaker.