⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

800 Amp Wire Size at 30 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 800 A load over a 30 ft (9.1 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.11%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.88V (0.37%)
Voltage at Load End239.7 VLoss: 0.27 V (370.8 W)
Power & Breaker (125%)332.55 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 800 Amps at 30 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A130.36 V (54.32%)109.6 V215.03 V (89.6%)180629.2 WDrop/Amp High
12 AWG3.31 mm²20 A81.92 V (34.13%)158.1 V135.12 V (56.3%)113507.2 WDrop/Amp High
10 AWG5.26 mm²30 A51.55 V (21.48%)188.5 V85.03 V (35.43%)71427.5 WDrop/Amp High
8 AWG8.37 mm²50 A32.39 V (13.5%)207.6 V53.44 V (22.27%)44887.5 WDrop/Amp High
6 AWG13.3 mm²65 A20.39 V (8.49%)219.6 V33.63 V (14.01%)28248.8 WDrop/Amp High
4 AWG21.15 mm²85 A12.82 V (5.34%)227.2 V21.15 V (8.81%)17764.0 WDrop/Amp High
3 AWG26.67 mm²100 A10.17 V (4.24%)229.8 V16.77 V (6.99%)14087.3 WDrop/Amp High
2 AWG33.62 mm²115 A8.06 V (3.36%)231.9 V13.3 V (5.54%)11175.2 WDrop/Amp High
1 AWG42.41 mm²130 A6.39 V (2.66%)233.6 V10.55 V (4.39%)8859.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A5.07 V (2.11%)234.9 V8.36 V (3.48%)7023.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A4.02 V (1.68%)236.0 V6.63 V (2.76%)5571.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A3.19 V (1.33%)236.8 V5.26 V (2.19%)4419.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.53 V (1.05%)237.5 V4.17 V (1.74%)3504.7 WDrop/Amp High
250 kcmil126.7 mm²255 A2.14 V (0.89%)237.9 V3.53 V (1.47%)2965.3 WDrop/Amp High
300 kcmil152.0 mm²285 A1.78 V (0.74%)238.2 V2.94 V (1.23%)2471.8 WDrop/Amp High
350 kcmil177.3 mm²310 A1.53 V (0.64%)238.5 V2.52 V (1.05%)2119.1 WDrop/Amp High
400 kcmil202.7 mm²335 A1.34 V (0.56%)238.7 V2.21 V (0.92%)1853.5 WDrop/Amp High
500 kcmil253.4 mm²380 A1.07 V (0.45%)238.9 V1.77 V (0.74%)1482.7 WDrop/Amp High
600 kcmil304.0 mm²420 A0.89 V (0.37%)239.1 V1.47 V (0.61%)1235.9 WDrop/Amp High
750 kcmil380.0 mm²475 A0.71 V (0.3%)239.3 V1.18 V (0.49%)988.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.54 V (0.22%)239.5 V0.88 V (0.37%)741.5 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 800 amps at 30 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 800A load over 30 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.27V (0.11%) and delivers 239.7V at the load.

What size aluminum wire is required for 800 amps at 30 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.88V (0.37%).

What breaker size is needed for a 800A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (800A × 1.25 = 1000.0A), which corresponds to a standard 1000A circuit breaker.