🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

90 Amp Wire Size at 250 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 90 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)1 AWG42.41 mm² · Drop: 2.5%
Aluminum Wire (≤3% Drop)2/0 AWGDrop: 6.22V (2.59%)
Voltage at Load End234.0 VLoss: 5.99 V (934.3 W)
Power & Breaker (125%)37.41 kW125A Breaker Recommended

All AWG & kcmil Wire Gauges for 90 Amps at 250 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A122.21 V (50.92%)117.8 V201.59 V (84.0%)19050.7 WDrop/Amp High
12 AWG3.31 mm²20 A76.8 V (32.0%)163.2 V126.68 V (52.78%)11971.5 WDrop/Amp High
10 AWG5.26 mm²30 A48.33 V (20.14%)191.7 V79.72 V (33.22%)7533.4 WDrop/Amp High
8 AWG8.37 mm²50 A30.37 V (12.65%)209.6 V50.1 V (20.87%)4734.2 WDrop/Amp High
6 AWG13.3 mm²65 A19.11 V (7.96%)220.9 V31.53 V (13.14%)2979.4 WDrop/Amp High
4 AWG21.15 mm²85 A12.02 V (5.01%)228.0 V19.83 V (8.26%)1873.5 WDrop/Amp High
3 AWG26.67 mm²100 A9.53 V (3.97%)230.5 V15.72 V (6.55%)1485.8 W~ ≤5%
2 AWG33.62 mm²115 A7.56 V (3.15%)232.4 V12.47 V (5.2%)1178.6 W~ ≤5%
1 AWG42.41 mm²130 A5.99 V (2.5%)234.0 V9.89 V (4.12%)934.3 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A4.75 V (1.98%)235.2 V7.84 V (3.27%)740.8 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A3.77 V (1.57%)236.2 V6.22 V (2.59%)587.7 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A2.99 V (1.25%)237.0 V4.93 V (2.06%)466.1 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A2.37 V (0.99%)237.6 V3.91 V (1.63%)369.6 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A2.01 V (0.84%)238.0 V3.31 V (1.38%)312.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.67 V (0.7%)238.3 V2.76 V (1.15%)260.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.43 V (0.6%)238.6 V2.36 V (0.99%)223.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.25 V (0.52%)238.7 V2.07 V (0.86%)195.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.0 V (0.42%)239.0 V1.65 V (0.69%)156.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.84 V (0.35%)239.2 V1.38 V (0.57%)130.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.67 V (0.28%)239.3 V1.1 V (0.46%)104.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.5 V (0.21%)239.5 V0.83 V (0.34%)78.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 90 amps at 250 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 90A load over 250 feet one-way at 240V (3-Phase), you need 1 AWG copper wire. This produces a voltage drop of 5.99V (2.5%) and delivers 234.0V at the load.

What size aluminum wire is required for 90 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 2/0 AWG to maintain voltage drop at 6.22V (2.59%).

What breaker size is needed for a 90A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (90A × 1.25 = 112.5A), which corresponds to a standard 125A circuit breaker.