🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

90 Amp Wire Size at 120 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 90 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)3 AWG26.67 mm² · Drop: 1.91%
Aluminum Wire (≤3% Drop)2 AWGDrop: 5.99V (2.49%)
Voltage at Load End235.4 VLoss: 4.57 V (713.2 W)
Power & Breaker (125%)37.41 kW125A Breaker Recommended

All AWG & kcmil Wire Gauges for 90 Amps at 120 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A58.66 V (24.44%)181.3 V96.76 V (40.32%)9144.4 WDrop/Amp High
12 AWG3.31 mm²20 A36.86 V (15.36%)203.1 V60.81 V (25.34%)5746.3 WDrop/Amp High
10 AWG5.26 mm²30 A23.2 V (9.67%)216.8 V38.26 V (15.94%)3616.0 WDrop/Amp High
8 AWG8.37 mm²50 A14.58 V (6.07%)225.4 V24.05 V (10.02%)2272.4 WDrop/Amp High
6 AWG13.3 mm²65 A9.17 V (3.82%)230.8 V15.13 V (6.31%)1430.1 WDrop/Amp High
4 AWG21.15 mm²85 A5.77 V (2.4%)234.2 V9.52 V (3.97%)899.3 WDrop/Amp High
3 AWG26.67 mm²100 A4.57 V (1.91%)235.4 V7.55 V (3.14%)713.2 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A3.63 V (1.51%)236.4 V5.99 V (2.49%)565.7 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A2.88 V (1.2%)237.1 V4.75 V (1.98%)448.5 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A2.28 V (0.95%)237.7 V3.76 V (1.57%)355.6 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.81 V (0.75%)238.2 V2.98 V (1.24%)282.1 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.44 V (0.6%)238.6 V2.37 V (0.99%)223.7 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.14 V (0.47%)238.9 V1.88 V (0.78%)177.4 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.96 V (0.4%)239.0 V1.59 V (0.66%)150.1 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.8 V (0.33%)239.2 V1.32 V (0.55%)125.1 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.69 V (0.29%)239.3 V1.14 V (0.47%)107.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.6 V (0.25%)239.4 V0.99 V (0.41%)93.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.48 V (0.2%)239.5 V0.79 V (0.33%)75.1 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.4 V (0.17%)239.6 V0.66 V (0.28%)62.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.32 V (0.13%)239.7 V0.53 V (0.22%)50.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.24 V (0.1%)239.8 V0.4 V (0.17%)37.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 90 amps at 120 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 90A load over 120 feet one-way at 240V (3-Phase), you need 3 AWG copper wire. This produces a voltage drop of 4.57V (1.91%) and delivers 235.4V at the load.

What size aluminum wire is required for 90 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 2 AWG to maintain voltage drop at 5.99V (2.49%).

What breaker size is needed for a 90A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (90A × 1.25 = 112.5A), which corresponds to a standard 125A circuit breaker.