⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

900 Amp Wire Size at 300 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 900 A load over a 300 ft (91.4 m) one-way run.

Copper Wire (≤3% Drop)20× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.9%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 11.47V (95.55%)
Voltage at Load End11.7 VLoss: 0.35 V (312.8 W)
Power & Breaker (125%)10.8 kW1200A Breaker Recommended

All AWG & kcmil Wire Gauges for 900 Amps at 300 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1693.4 V (14111.65%)0.0 V2793.32 V (23277.63%)1524058.6 WDrop/Amp High
12 AWG3.31 mm²20 A1064.13 V (8867.75%)0.0 V1755.32 V (14627.64%)957716.6 WDrop/Amp High
10 AWG5.26 mm²30 A669.63 V (5580.27%)0.0 V1104.58 V (9204.84%)602669.6 WDrop/Amp High
8 AWG8.37 mm²50 A420.82 V (3506.84%)0.0 V694.16 V (5784.65%)378738.6 WDrop/Amp High
6 AWG13.3 mm²65 A264.83 V (2206.94%)0.0 V436.85 V (3640.41%)238349.0 WDrop/Amp High
4 AWG21.15 mm²85 A166.54 V (1387.81%)0.0 V274.71 V (2289.24%)149883.8 WDrop/Amp High
3 AWG26.67 mm²100 A132.07 V (1100.57%)0.0 V217.85 V (1815.43%)118861.7 WDrop/Amp High
2 AWG33.62 mm²115 A104.77 V (873.06%)0.0 V172.82 V (1440.14%)94290.4 WDrop/Amp High
1 AWG42.41 mm²130 A83.05 V (692.11%)0.0 V137.0 V (1141.65%)74747.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A65.85 V (548.74%)0.0 V108.62 V (905.17%)59264.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A52.24 V (435.3%)0.0 V86.16 V (718.04%)47012.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A41.43 V (345.28%)0.0 V68.35 V (569.55%)37290.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A32.86 V (273.81%)0.0 V54.2 V (451.66%)29571.3 WDrop/Amp High
250 kcmil126.7 mm²255 A27.8 V (231.67%)0.0 V45.86 V (382.14%)25020.1 WDrop/Amp High
300 kcmil152.0 mm²285 A23.17 V (193.11%)0.0 V38.22 V (318.54%)20855.5 WDrop/Amp High
350 kcmil177.3 mm²310 A19.87 V (165.55%)0.0 V32.77 V (273.08%)17879.5 WDrop/Amp High
400 kcmil202.7 mm²335 A17.38 V (144.81%)0.0 V28.66 V (238.86%)15639.1 WDrop/Amp High
500 kcmil253.4 mm²380 A13.9 V (115.83%)0.0 V22.93 V (191.07%)12510.0 WDrop/Amp High
600 kcmil304.0 mm²420 A11.59 V (96.55%)0.4 V19.11 V (159.27%)10427.8 WDrop/Amp High
750 kcmil380.0 mm²475 A9.27 V (77.24%)2.7 V15.29 V (127.41%)8342.2 WDrop/Amp High
1000 kcmil506.7 mm²545 A6.95 V (57.93%)5.0 V11.47 V (95.55%)6256.3 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 900 amps at 300 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 900A load over 300 feet one-way at 12V (DC), you need 20× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.35V (2.9%) and delivers 11.7V at the load.

What size aluminum wire is required for 900 amps at 300 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 11.47V (95.55%).

What breaker size is needed for a 900A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (900A × 1.25 = 1125.0A), which corresponds to a standard 1200A circuit breaker.