10 Amp Cable Size at 70 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 10 A over 70 m (229.7 ft).

Copper Cable (≤3% Drop)25 mm²Drop: 1.2V (2.5%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 1.41V (2.94%)
Voltage at Load46.8 VLine Loss: 12.0 W
Max Power & Breaker0.48 kW10A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 10A at 70m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A19.97 V (41.61%)28.0 V32.95 V (68.64%)199.7 WDrop High
2.5 mm²24 A18 A11.98 V (24.97%)36.0 V19.77 V (41.18%)119.8 WDrop High
4 mm²32 A25 A7.49 V (15.6%)40.5 V12.36 V (25.74%)74.9 WDrop High
6 mm²41 A32 A4.99 V (10.4%)43.0 V8.24 V (17.16%)49.9 WDrop High
10 mm²57 A44 A3.0 V (6.24%)45.0 V4.94 V (10.3%)30.0 WDrop High
16 mm²76 A59 A1.87 V (3.9%)46.1 V3.09 V (6.43%)18.7 W~ ≤5%
25 mm²101 A78 A1.2 V (2.5%)46.8 V1.98 V (4.12%)12.0 W✓ OK (≤3%)
35 mm²125 A97 A0.86 V (1.78%)47.1 V1.41 V (2.94%)8.6 W✓ OK (≤3%)
50 mm²151 A118 A0.6 V (1.25%)47.4 V0.99 V (2.06%)6.0 W✓ OK (≤3%)
70 mm²192 A150 A0.43 V (0.89%)47.6 V0.71 V (1.47%)4.3 W✓ OK (≤3%)
95 mm²232 A181 A0.32 V (0.66%)47.7 V0.52 V (1.08%)3.2 W✓ OK (≤3%)
120 mm²269 A210 A0.25 V (0.52%)47.8 V0.41 V (0.86%)2.5 W✓ OK (≤3%)
150 mm²309 A241 A0.2 V (0.42%)47.8 V0.33 V (0.69%)2.0 W✓ OK (≤3%)
185 mm²353 A275 A0.16 V (0.34%)47.8 V0.27 V (0.56%)1.6 W✓ OK (≤3%)
240 mm²415 A324 A0.12 V (0.26%)47.9 V0.21 V (0.43%)1.2 W✓ OK (≤3%)
300 mm²477 A372 A0.1 V (0.21%)47.9 V0.16 V (0.34%)1.0 W✓ OK (≤3%)
400 mm²570 A445 A0.07 V (0.16%)47.9 V0.12 V (0.26%)0.7 W✓ OK (≤3%)

FAQ — 10 Amp Cable Size at 70 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 10A at 70 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 25 mm² copper cable for 10A over 70m at 48V (voltage drop: 1.2V or 2.5%).

What is the power capacity of 10A at 48V?

At unity power factor, 10A at 48V supports 0.48 kW with a standard 10A circuit breaker.