10 Amp Cable Size at 175 Meters (400V Three-Phase (IEC European Grid))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 10 A over 175 m (574.1 ft).
Copper Cable (≤3% Drop)6 mm²Drop: 10.81V (2.7%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 10.7V (2.67%)
Voltage at Load389.2 VLine Loss: 187.2 W
Max Power & Breaker6.93 kW10A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 10A at 175m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 43.24 V (10.81%) | 356.8 V | 71.33 V (17.83%) | 749.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 25.95 V (6.49%) | 374.1 V | 42.8 V (10.7%) | 449.4 W | Drop High |
| 4 mm² | 32 A | 25 A | 16.22 V (4.05%) | 383.8 V | 26.75 V (6.69%) | 280.9 W | ~ ≤5% |
| 6 mm² | 41 A | 32 A | 10.81 V (2.7%) | 389.2 V | 17.83 V (4.46%) | 187.2 W | ✓ OK (≤3%) |
| 10 mm² | 57 A | 44 A | 6.49 V (1.62%) | 393.5 V | 10.7 V (2.67%) | 112.3 W | ✓ OK (≤3%) |
| 16 mm² | 76 A | 59 A | 4.05 V (1.01%) | 395.9 V | 6.69 V (1.67%) | 70.2 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 2.59 V (0.65%) | 397.4 V | 4.28 V (1.07%) | 44.9 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 1.85 V (0.46%) | 398.1 V | 3.06 V (0.76%) | 32.1 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 1.3 V (0.32%) | 398.7 V | 2.14 V (0.53%) | 22.5 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.93 V (0.23%) | 399.1 V | 1.53 V (0.38%) | 16.0 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.68 V (0.17%) | 399.3 V | 1.13 V (0.28%) | 11.8 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.54 V (0.14%) | 399.5 V | 0.89 V (0.22%) | 9.4 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.43 V (0.11%) | 399.6 V | 0.71 V (0.18%) | 7.5 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.35 V (0.09%) | 399.6 V | 0.58 V (0.14%) | 6.1 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.27 V (0.07%) | 399.7 V | 0.45 V (0.11%) | 4.7 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.22 V (0.05%) | 399.8 V | 0.36 V (0.09%) | 3.7 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.16 V (0.04%) | 399.8 V | 0.27 V (0.07%) | 2.8 W | ✓ OK (≤3%) |
FAQ — 10 Amp Cable Size at 175 Meters (400V Three-Phase (IEC European Grid))
What mm² cable size is required for 10A at 175 meters (400V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 6 mm² copper cable for 10A over 175m at 400V (voltage drop: 10.81V or 2.7%).
What is the power capacity of 10A at 400V?
At unity power factor, 10A at 400V supports 6.93 kW with a standard 10A circuit breaker.
Related Lengths & Currents (400V)
10A · 5m (400V)10A · 10m (400V)10A · 15m (400V)10A · 20m (400V)10A · 25m (400V)10A · 30m (400V)10A · 35m (400V)10A · 40m (400V)10A · 45m (400V)10A · 50m (400V)10A · 60m (400V)10A · 70m (400V)16A · 175m (400V)20A · 175m (400V)25A · 175m (400V)32A · 175m (400V)40A · 175m (400V)50A · 175m (400V)63A · 175m (400V)80A · 175m (400V)100A · 175m (400V)125A · 175m (400V)160A · 175m (400V)200A · 175m (400V)