25 Amp Cable Size at 175 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 25 A over 175 m (574.1 ft).

Copper Cable (≤3% Drop)16 mm²Drop: 10.14V (2.53%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 10.7V (2.67%)
Voltage at Load389.9 VLine Loss: 438.9 W
Max Power & Breaker17.32 kW25A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A108.11 V (27.03%)291.9 V178.33 V (44.58%)4681.2 WDrop High
2.5 mm²24 A18 A64.87 V (16.22%)335.1 V107.0 V (26.75%)2808.7 WDrop High
4 mm²32 A25 A40.54 V (10.14%)359.5 V66.87 V (16.72%)1755.5 WDrop High
6 mm²41 A32 A27.03 V (6.76%)373.0 V44.58 V (11.15%)1170.3 WDrop High
10 mm²57 A44 A16.22 V (4.05%)383.8 V26.75 V (6.69%)702.2 W~ ≤5%
16 mm²76 A59 A10.14 V (2.53%)389.9 V16.72 V (4.18%)438.9 W✓ OK (≤3%)
25 mm²101 A78 A6.49 V (1.62%)393.5 V10.7 V (2.67%)280.9 W✓ OK (≤3%)
35 mm²125 A97 A4.63 V (1.16%)395.4 V7.64 V (1.91%)200.6 W✓ OK (≤3%)
50 mm²151 A118 A3.24 V (0.81%)396.8 V5.35 V (1.34%)140.4 W✓ OK (≤3%)
70 mm²192 A150 A2.32 V (0.58%)397.7 V3.82 V (0.96%)100.3 W✓ OK (≤3%)
95 mm²232 A181 A1.71 V (0.43%)398.3 V2.82 V (0.7%)73.9 W✓ OK (≤3%)
120 mm²269 A210 A1.35 V (0.34%)398.6 V2.23 V (0.56%)58.5 W✓ OK (≤3%)
150 mm²309 A241 A1.08 V (0.27%)398.9 V1.78 V (0.45%)46.8 W✓ OK (≤3%)
185 mm²353 A275 A0.88 V (0.22%)399.1 V1.45 V (0.36%)38.0 W✓ OK (≤3%)
240 mm²415 A324 A0.68 V (0.17%)399.3 V1.11 V (0.28%)29.3 W✓ OK (≤3%)
300 mm²477 A372 A0.54 V (0.14%)399.5 V0.89 V (0.22%)23.4 W✓ OK (≤3%)
400 mm²570 A445 A0.41 V (0.1%)399.6 V0.67 V (0.17%)17.6 W✓ OK (≤3%)

FAQ — 25 Amp Cable Size at 175 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 25A at 175 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 16 mm² copper cable for 25A over 175m at 400V (voltage drop: 10.14V or 2.53%).

What is the power capacity of 25A at 400V?

At unity power factor, 25A at 400V supports 17.32 kW with a standard 25A circuit breaker.