160 Amp Cable Size at 175 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 160 A over 175 m (574.1 ft).

Copper Cable (≤3% Drop)95 mm²Drop: 10.92V (2.73%)
Aluminum Cable (≤3% Drop)150 mm²Drop: 11.41V (2.85%)
Voltage at Load389.1 VLine Loss: 3027.5 W
Max Power & Breaker110.85 kW160A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 160A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A691.9 V (172.97%)0.0 V1141.31 V (285.33%)191744.0 WDrop High
2.5 mm²24 A18 A415.14 V (103.78%)0.0 V684.78 V (171.2%)115046.4 WDrop High
4 mm²32 A25 A259.46 V (64.87%)140.5 V427.99 V (107.0%)71904.0 WDrop High
6 mm²41 A32 A172.97 V (43.24%)227.0 V285.33 V (71.33%)47936.0 WDrop High
10 mm²57 A44 A103.78 V (25.95%)296.2 V171.2 V (42.8%)28761.6 WDrop High
16 mm²76 A59 A64.87 V (16.22%)335.1 V107.0 V (26.75%)17976.0 WDrop High
25 mm²101 A78 A41.51 V (10.38%)358.5 V68.48 V (17.12%)11504.6 WDrop High
35 mm²125 A97 A29.65 V (7.41%)370.3 V48.91 V (12.23%)8217.6 WDrop High
50 mm²151 A118 A20.76 V (5.19%)379.2 V34.24 V (8.56%)5752.3 WDrop High
70 mm²192 A150 A14.83 V (3.71%)385.2 V24.46 V (6.11%)4108.8 W~ ≤5%
95 mm²232 A181 A10.92 V (2.73%)389.1 V18.02 V (4.51%)3027.5 W✓ OK (≤3%)
120 mm²269 A210 A8.65 V (2.16%)391.4 V14.27 V (3.57%)2396.8 W✓ OK (≤3%)
150 mm²309 A241 A6.92 V (1.73%)393.1 V11.41 V (2.85%)1917.4 W✓ OK (≤3%)
185 mm²353 A275 A5.61 V (1.4%)394.4 V9.25 V (2.31%)1554.7 W✓ OK (≤3%)
240 mm²415 A324 A4.32 V (1.08%)395.7 V7.13 V (1.78%)1198.4 W✓ OK (≤3%)
300 mm²477 A372 A3.46 V (0.86%)396.5 V5.71 V (1.43%)958.7 W✓ OK (≤3%)
400 mm²570 A445 A2.59 V (0.65%)397.4 V4.28 V (1.07%)719.0 W✓ OK (≤3%)

FAQ — 160 Amp Cable Size at 175 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 160A at 175 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 95 mm² copper cable for 160A over 175m at 400V (voltage drop: 10.92V or 2.73%).

What is the power capacity of 160A at 400V?

At unity power factor, 160A at 400V supports 110.85 kW with a standard 160A circuit breaker.