⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

10 Amp Cable Size at 45 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 10 A over 45 m (147.6 ft).

Copper Cable (≤3% Drop)1.5 mm²Drop: 11.12V (1.61%)
Aluminum Cable (≤3% Drop)1.5 mm²Drop: 18.34V (2.66%)
Voltage at Load678.9 VLine Loss: 192.6 W
Max Power & Breaker11.95 kW10A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 10A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A11.12 V (1.61%)678.9 V18.34 V (2.66%)192.6 W✓ OK (≤3%)
2.5 mm²24 A18 A6.67 V (0.97%)683.3 V11.01 V (1.59%)115.6 W✓ OK (≤3%)
4 mm²32 A25 A4.17 V (0.6%)685.8 V6.88 V (1.0%)72.2 W✓ OK (≤3%)
6 mm²41 A32 A2.78 V (0.4%)687.2 V4.59 V (0.66%)48.1 W✓ OK (≤3%)
10 mm²57 A44 A1.67 V (0.24%)688.3 V2.75 V (0.4%)28.9 W✓ OK (≤3%)
16 mm²76 A59 A1.04 V (0.15%)689.0 V1.72 V (0.25%)18.1 W✓ OK (≤3%)
25 mm²101 A78 A0.67 V (0.1%)689.3 V1.1 V (0.16%)11.6 W✓ OK (≤3%)
35 mm²125 A97 A0.48 V (0.07%)689.5 V0.79 V (0.11%)8.3 W✓ OK (≤3%)
50 mm²151 A118 A0.33 V (0.05%)689.7 V0.55 V (0.08%)5.8 W✓ OK (≤3%)
70 mm²192 A150 A0.24 V (0.03%)689.8 V0.39 V (0.06%)4.1 W✓ OK (≤3%)
95 mm²232 A181 A0.18 V (0.03%)689.8 V0.29 V (0.04%)3.0 W✓ OK (≤3%)
120 mm²269 A210 A0.14 V (0.02%)689.9 V0.23 V (0.03%)2.4 W✓ OK (≤3%)
150 mm²309 A241 A0.11 V (0.02%)689.9 V0.18 V (0.03%)1.9 W✓ OK (≤3%)
185 mm²353 A275 A0.09 V (0.01%)689.9 V0.15 V (0.02%)1.6 W✓ OK (≤3%)
240 mm²415 A324 A0.07 V (0.01%)689.9 V0.11 V (0.02%)1.2 W✓ OK (≤3%)
300 mm²477 A372 A0.06 V (0.01%)689.9 V0.09 V (0.01%)1.0 W✓ OK (≤3%)
400 mm²570 A445 A0.04 V (0.01%)690.0 V0.07 V (0.01%)0.7 W✓ OK (≤3%)

FAQ — 10 Amp Cable Size at 45 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 10A at 45 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 1.5 mm² copper cable for 10A over 45m at 690V (voltage drop: 11.12V or 1.61%).

What is the power capacity of 10A at 690V?

At unity power factor, 10A at 690V supports 11.95 kW with a standard 10A circuit breaker.