⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

40 Amp Cable Size at 45 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 40 A over 45 m (147.6 ft).

Copper Cable (≤3% Drop)6 mm²Drop: 11.12V (1.61%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 11.01V (1.59%)
Voltage at Load678.9 VLine Loss: 770.4 W
Max Power & Breaker47.8 kW40A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 40A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A44.48 V (6.45%)645.5 V73.37 V (10.63%)3081.6 WDrop High
2.5 mm²24 A18 A26.69 V (3.87%)663.3 V44.02 V (6.38%)1849.0 WDrop High
4 mm²32 A25 A16.68 V (2.42%)673.3 V27.51 V (3.99%)1155.6 WDrop High
6 mm²41 A32 A11.12 V (1.61%)678.9 V18.34 V (2.66%)770.4 W✓ OK (≤3%)
10 mm²57 A44 A6.67 V (0.97%)683.3 V11.01 V (1.59%)462.2 W✓ OK (≤3%)
16 mm²76 A59 A4.17 V (0.6%)685.8 V6.88 V (1.0%)288.9 W✓ OK (≤3%)
25 mm²101 A78 A2.67 V (0.39%)687.3 V4.4 V (0.64%)184.9 W✓ OK (≤3%)
35 mm²125 A97 A1.91 V (0.28%)688.1 V3.14 V (0.46%)132.1 W✓ OK (≤3%)
50 mm²151 A118 A1.33 V (0.19%)688.7 V2.2 V (0.32%)92.4 W✓ OK (≤3%)
70 mm²192 A150 A0.95 V (0.14%)689.0 V1.57 V (0.23%)66.0 W✓ OK (≤3%)
95 mm²232 A181 A0.7 V (0.1%)689.3 V1.16 V (0.17%)48.7 W✓ OK (≤3%)
120 mm²269 A210 A0.56 V (0.08%)689.4 V0.92 V (0.13%)38.5 W✓ OK (≤3%)
150 mm²309 A241 A0.44 V (0.06%)689.6 V0.73 V (0.11%)30.8 W✓ OK (≤3%)
185 mm²353 A275 A0.36 V (0.05%)689.6 V0.59 V (0.09%)25.0 W✓ OK (≤3%)
240 mm²415 A324 A0.28 V (0.04%)689.7 V0.46 V (0.07%)19.3 W✓ OK (≤3%)
300 mm²477 A372 A0.22 V (0.03%)689.8 V0.37 V (0.05%)15.4 W✓ OK (≤3%)
400 mm²570 A445 A0.17 V (0.02%)689.8 V0.28 V (0.04%)11.6 W✓ OK (≤3%)

FAQ — 40 Amp Cable Size at 45 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 40A at 45 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 6 mm² copper cable for 40A over 45m at 690V (voltage drop: 11.12V or 1.61%).

What is the power capacity of 40A at 690V?

At unity power factor, 40A at 690V supports 47.8 kW with a standard 40A circuit breaker.