25 Amp Cable Size at 45 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 25 A over 45 m (147.6 ft).

Copper Cable (≤3% Drop)4 mm²Drop: 10.42V (1.51%)
Aluminum Cable (≤3% Drop)4 mm²Drop: 17.2V (2.49%)
Voltage at Load679.6 VLine Loss: 451.4 W
Max Power & Breaker29.88 kW25A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A27.8 V (4.03%)662.2 V45.86 V (6.65%)1203.8 WDrop High
2.5 mm²24 A18 A16.68 V (2.42%)673.3 V27.51 V (3.99%)722.2 WDrop High
4 mm²32 A25 A10.42 V (1.51%)679.6 V17.2 V (2.49%)451.4 W✓ OK (≤3%)
6 mm²41 A32 A6.95 V (1.01%)683.1 V11.46 V (1.66%)300.9 W✓ OK (≤3%)
10 mm²57 A44 A4.17 V (0.6%)685.8 V6.88 V (1.0%)180.6 W✓ OK (≤3%)
16 mm²76 A59 A2.61 V (0.38%)687.4 V4.3 V (0.62%)112.9 W✓ OK (≤3%)
25 mm²101 A78 A1.67 V (0.24%)688.3 V2.75 V (0.4%)72.2 W✓ OK (≤3%)
35 mm²125 A97 A1.19 V (0.17%)688.8 V1.97 V (0.28%)51.6 W✓ OK (≤3%)
50 mm²151 A118 A0.83 V (0.12%)689.2 V1.38 V (0.2%)36.1 W✓ OK (≤3%)
70 mm²192 A150 A0.6 V (0.09%)689.4 V0.98 V (0.14%)25.8 W✓ OK (≤3%)
95 mm²232 A181 A0.44 V (0.06%)689.6 V0.72 V (0.1%)19.0 W✓ OK (≤3%)
120 mm²269 A210 A0.35 V (0.05%)689.7 V0.57 V (0.08%)15.0 W✓ OK (≤3%)
150 mm²309 A241 A0.28 V (0.04%)689.7 V0.46 V (0.07%)12.0 W✓ OK (≤3%)
185 mm²353 A275 A0.23 V (0.03%)689.8 V0.37 V (0.05%)9.8 W✓ OK (≤3%)
240 mm²415 A324 A0.17 V (0.03%)689.8 V0.29 V (0.04%)7.5 W✓ OK (≤3%)
300 mm²477 A372 A0.14 V (0.02%)689.9 V0.23 V (0.03%)6.0 W✓ OK (≤3%)
400 mm²570 A445 A0.1 V (0.02%)689.9 V0.17 V (0.02%)4.5 W✓ OK (≤3%)

FAQ — 25 Amp Cable Size at 45 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 25A at 45 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 4 mm² copper cable for 25A over 45m at 690V (voltage drop: 10.42V or 1.51%).

What is the power capacity of 25A at 690V?

At unity power factor, 25A at 690V supports 29.88 kW with a standard 25A circuit breaker.