⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

10 Amp Cable Size at 45 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 10 A over 45 m (147.6 ft).

Copper Cable (≤3% Drop)4 mm²Drop: 4.81V (2.09%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 5.29V (2.3%)
Voltage at Load225.2 VLine Loss: 48.1 W
Max Power & Breaker2.3 kW10A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 10A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A12.84 V (5.58%)217.2 V21.18 V (9.21%)128.4 WDrop High
2.5 mm²24 A18 A7.7 V (3.35%)222.3 V12.71 V (5.53%)77.0 W~ ≤5%
4 mm²32 A25 A4.81 V (2.09%)225.2 V7.94 V (3.45%)48.1 W✓ OK (≤3%)
6 mm²41 A32 A3.21 V (1.4%)226.8 V5.29 V (2.3%)32.1 W✓ OK (≤3%)
10 mm²57 A44 A1.93 V (0.84%)228.1 V3.18 V (1.38%)19.3 W✓ OK (≤3%)
16 mm²76 A59 A1.2 V (0.52%)228.8 V1.99 V (0.86%)12.0 W✓ OK (≤3%)
25 mm²101 A78 A0.77 V (0.33%)229.2 V1.27 V (0.55%)7.7 W✓ OK (≤3%)
35 mm²125 A97 A0.55 V (0.24%)229.4 V0.91 V (0.39%)5.5 W✓ OK (≤3%)
50 mm²151 A118 A0.39 V (0.17%)229.6 V0.64 V (0.28%)3.9 W✓ OK (≤3%)
70 mm²192 A150 A0.28 V (0.12%)229.7 V0.45 V (0.2%)2.8 W✓ OK (≤3%)
95 mm²232 A181 A0.2 V (0.09%)229.8 V0.33 V (0.15%)2.0 W✓ OK (≤3%)
120 mm²269 A210 A0.16 V (0.07%)229.8 V0.26 V (0.12%)1.6 W✓ OK (≤3%)
150 mm²309 A241 A0.13 V (0.06%)229.9 V0.21 V (0.09%)1.3 W✓ OK (≤3%)
185 mm²353 A275 A0.1 V (0.05%)229.9 V0.17 V (0.07%)1.0 W✓ OK (≤3%)
240 mm²415 A324 A0.08 V (0.03%)229.9 V0.13 V (0.06%)0.8 W✓ OK (≤3%)
300 mm²477 A372 A0.06 V (0.03%)229.9 V0.11 V (0.05%)0.6 W✓ OK (≤3%)
400 mm²570 A445 A0.05 V (0.02%)230.0 V0.08 V (0.03%)0.5 W✓ OK (≤3%)

FAQ — 10 Amp Cable Size at 45 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 10A at 45 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 4 mm² copper cable for 10A over 45m at 230V (voltage drop: 4.81V or 2.09%).

What is the power capacity of 10A at 230V?

At unity power factor, 10A at 230V supports 2.3 kW with a standard 10A circuit breaker.