10 Amp Cable Size at 60 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 10 A over 60 m (196.9 ft).

Copper Cable (≤3% Drop)50 mm²Drop: 0.51V (2.14%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 0.61V (2.52%)
Voltage at Load23.5 VLine Loss: 5.1 W
Max Power & Breaker0.24 kW10A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 10A at 60m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A17.12 V (71.33%)6.9 V28.24 V (117.67%)171.2 WDrop High
2.5 mm²24 A18 A10.27 V (42.8%)13.7 V16.94 V (70.6%)102.7 WDrop High
4 mm²32 A25 A6.42 V (26.75%)17.6 V10.59 V (44.12%)64.2 WDrop High
6 mm²41 A32 A4.28 V (17.83%)19.7 V7.06 V (29.42%)42.8 WDrop High
10 mm²57 A44 A2.57 V (10.7%)21.4 V4.24 V (17.65%)25.7 WDrop High
16 mm²76 A59 A1.6 V (6.69%)22.4 V2.65 V (11.03%)16.1 WDrop High
25 mm²101 A78 A1.03 V (4.28%)23.0 V1.69 V (7.06%)10.3 W~ ≤5%
35 mm²125 A97 A0.73 V (3.06%)23.3 V1.21 V (5.04%)7.3 W~ ≤5%
50 mm²151 A118 A0.51 V (2.14%)23.5 V0.85 V (3.53%)5.1 W✓ OK (≤3%)
70 mm²192 A150 A0.37 V (1.53%)23.6 V0.61 V (2.52%)3.7 W✓ OK (≤3%)
95 mm²232 A181 A0.27 V (1.13%)23.7 V0.45 V (1.86%)2.7 W✓ OK (≤3%)
120 mm²269 A210 A0.21 V (0.89%)23.8 V0.35 V (1.47%)2.1 W✓ OK (≤3%)
150 mm²309 A241 A0.17 V (0.71%)23.8 V0.28 V (1.18%)1.7 W✓ OK (≤3%)
185 mm²353 A275 A0.14 V (0.58%)23.9 V0.23 V (0.95%)1.4 W✓ OK (≤3%)
240 mm²415 A324 A0.11 V (0.45%)23.9 V0.18 V (0.74%)1.1 W✓ OK (≤3%)
300 mm²477 A372 A0.09 V (0.36%)23.9 V0.14 V (0.59%)0.9 W✓ OK (≤3%)
400 mm²570 A445 A0.06 V (0.27%)23.9 V0.11 V (0.44%)0.6 W✓ OK (≤3%)

FAQ — 10 Amp Cable Size at 60 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 10A at 60 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 50 mm² copper cable for 10A over 60m at 24V (voltage drop: 0.51V or 2.14%).

What is the power capacity of 10A at 24V?

At unity power factor, 10A at 24V supports 0.24 kW with a standard 10A circuit breaker.