10 Amp Cable Size at 25 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 10 A over 25 m (82.0 ft).

Copper Cable (≤3% Drop)16 mm²Drop: 0.67V (2.79%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 0.71V (2.94%)
Voltage at Load23.3 VLine Loss: 6.7 W
Max Power & Breaker0.24 kW10A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 10A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A7.13 V (29.72%)16.9 V11.77 V (49.03%)71.3 WDrop High
2.5 mm²24 A18 A4.28 V (17.83%)19.7 V7.06 V (29.42%)42.8 WDrop High
4 mm²32 A25 A2.67 V (11.15%)21.3 V4.41 V (18.39%)26.7 WDrop High
6 mm²41 A32 A1.78 V (7.43%)22.2 V2.94 V (12.26%)17.8 WDrop High
10 mm²57 A44 A1.07 V (4.46%)22.9 V1.76 V (7.35%)10.7 W~ ≤5%
16 mm²76 A59 A0.67 V (2.79%)23.3 V1.1 V (4.6%)6.7 W✓ OK (≤3%)
25 mm²101 A78 A0.43 V (1.78%)23.6 V0.71 V (2.94%)4.3 W✓ OK (≤3%)
35 mm²125 A97 A0.31 V (1.27%)23.7 V0.5 V (2.1%)3.1 W✓ OK (≤3%)
50 mm²151 A118 A0.21 V (0.89%)23.8 V0.35 V (1.47%)2.1 W✓ OK (≤3%)
70 mm²192 A150 A0.15 V (0.64%)23.8 V0.25 V (1.05%)1.5 W✓ OK (≤3%)
95 mm²232 A181 A0.11 V (0.47%)23.9 V0.19 V (0.77%)1.1 W✓ OK (≤3%)
120 mm²269 A210 A0.09 V (0.37%)23.9 V0.15 V (0.61%)0.9 W✓ OK (≤3%)
150 mm²309 A241 A0.07 V (0.3%)23.9 V0.12 V (0.49%)0.7 W✓ OK (≤3%)
185 mm²353 A275 A0.06 V (0.24%)23.9 V0.1 V (0.4%)0.6 W✓ OK (≤3%)
240 mm²415 A324 A0.04 V (0.19%)24.0 V0.07 V (0.31%)0.4 W✓ OK (≤3%)
300 mm²477 A372 A0.04 V (0.15%)24.0 V0.06 V (0.25%)0.4 W✓ OK (≤3%)
400 mm²570 A445 A0.03 V (0.11%)24.0 V0.04 V (0.18%)0.3 W✓ OK (≤3%)

FAQ — 10 Amp Cable Size at 25 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 10A at 25 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 16 mm² copper cable for 10A over 25m at 24V (voltage drop: 0.67V or 2.79%).

What is the power capacity of 10A at 24V?

At unity power factor, 10A at 24V supports 0.24 kW with a standard 10A circuit breaker.