10 Amp Cable Size at 70 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 10 A over 70 m (229.7 ft).

Copper Cable (≤3% Drop)50 mm²Drop: 0.6V (2.5%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 0.71V (2.94%)
Voltage at Load23.4 VLine Loss: 6.0 W
Max Power & Breaker0.24 kW10A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 10A at 70m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A19.97 V (83.22%)4.0 V32.95 V (137.28%)199.7 WDrop High
2.5 mm²24 A18 A11.98 V (49.93%)12.0 V19.77 V (82.37%)119.8 WDrop High
4 mm²32 A25 A7.49 V (31.21%)16.5 V12.36 V (51.48%)74.9 WDrop High
6 mm²41 A32 A4.99 V (20.81%)19.0 V8.24 V (34.32%)49.9 WDrop High
10 mm²57 A44 A3.0 V (12.48%)21.0 V4.94 V (20.59%)30.0 WDrop High
16 mm²76 A59 A1.87 V (7.8%)22.1 V3.09 V (12.87%)18.7 WDrop High
25 mm²101 A78 A1.2 V (4.99%)22.8 V1.98 V (8.24%)12.0 W~ ≤5%
35 mm²125 A97 A0.86 V (3.57%)23.1 V1.41 V (5.88%)8.6 W~ ≤5%
50 mm²151 A118 A0.6 V (2.5%)23.4 V0.99 V (4.12%)6.0 W✓ OK (≤3%)
70 mm²192 A150 A0.43 V (1.78%)23.6 V0.71 V (2.94%)4.3 W✓ OK (≤3%)
95 mm²232 A181 A0.32 V (1.31%)23.7 V0.52 V (2.17%)3.2 W✓ OK (≤3%)
120 mm²269 A210 A0.25 V (1.04%)23.8 V0.41 V (1.72%)2.5 W✓ OK (≤3%)
150 mm²309 A241 A0.2 V (0.83%)23.8 V0.33 V (1.37%)2.0 W✓ OK (≤3%)
185 mm²353 A275 A0.16 V (0.67%)23.8 V0.27 V (1.11%)1.6 W✓ OK (≤3%)
240 mm²415 A324 A0.12 V (0.52%)23.9 V0.21 V (0.86%)1.2 W✓ OK (≤3%)
300 mm²477 A372 A0.1 V (0.42%)23.9 V0.16 V (0.69%)1.0 W✓ OK (≤3%)
400 mm²570 A445 A0.07 V (0.31%)23.9 V0.12 V (0.51%)0.7 W✓ OK (≤3%)

FAQ — 10 Amp Cable Size at 70 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 10A at 70 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 50 mm² copper cable for 10A over 70m at 24V (voltage drop: 0.6V or 2.5%).

What is the power capacity of 10A at 24V?

At unity power factor, 10A at 24V supports 0.24 kW with a standard 10A circuit breaker.