10 Amp Cable Size at 50 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 10 A over 50 m (164.0 ft).

Copper Cable (≤3% Drop)1.5 mm²Drop: 12.36V (2.98%)
Aluminum Cable (≤3% Drop)2.5 mm²Drop: 12.23V (2.95%)
Voltage at Load402.6 VLine Loss: 214.0 W
Max Power & Breaker7.19 kW10A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 10A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A12.36 V (2.98%)402.6 V20.38 V (4.91%)214.0 W✓ OK (≤3%)
2.5 mm²24 A18 A7.41 V (1.79%)407.6 V12.23 V (2.95%)128.4 W✓ OK (≤3%)
4 mm²32 A25 A4.63 V (1.12%)410.4 V7.64 V (1.84%)80.2 W✓ OK (≤3%)
6 mm²41 A32 A3.09 V (0.74%)411.9 V5.1 V (1.23%)53.5 W✓ OK (≤3%)
10 mm²57 A44 A1.85 V (0.45%)413.1 V3.06 V (0.74%)32.1 W✓ OK (≤3%)
16 mm²76 A59 A1.16 V (0.28%)413.8 V1.91 V (0.46%)20.1 W✓ OK (≤3%)
25 mm²101 A78 A0.74 V (0.18%)414.3 V1.22 V (0.29%)12.8 W✓ OK (≤3%)
35 mm²125 A97 A0.53 V (0.13%)414.5 V0.87 V (0.21%)9.2 W✓ OK (≤3%)
50 mm²151 A118 A0.37 V (0.09%)414.6 V0.61 V (0.15%)6.4 W✓ OK (≤3%)
70 mm²192 A150 A0.26 V (0.06%)414.7 V0.44 V (0.11%)4.6 W✓ OK (≤3%)
95 mm²232 A181 A0.2 V (0.05%)414.8 V0.32 V (0.08%)3.4 W✓ OK (≤3%)
120 mm²269 A210 A0.15 V (0.04%)414.8 V0.25 V (0.06%)2.7 W✓ OK (≤3%)
150 mm²309 A241 A0.12 V (0.03%)414.9 V0.2 V (0.05%)2.1 W✓ OK (≤3%)
185 mm²353 A275 A0.1 V (0.02%)414.9 V0.17 V (0.04%)1.7 W✓ OK (≤3%)
240 mm²415 A324 A0.08 V (0.02%)414.9 V0.13 V (0.03%)1.3 W✓ OK (≤3%)
300 mm²477 A372 A0.06 V (0.01%)414.9 V0.1 V (0.02%)1.1 W✓ OK (≤3%)
400 mm²570 A445 A0.05 V (0.01%)415.0 V0.08 V (0.02%)0.8 W✓ OK (≤3%)

FAQ — 10 Amp Cable Size at 50 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 10A at 50 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 1.5 mm² copper cable for 10A over 50m at 415V (voltage drop: 12.36V or 2.98%).

What is the power capacity of 10A at 415V?

At unity power factor, 10A at 415V supports 7.19 kW with a standard 10A circuit breaker.