10 Amp Cable Size at 60 Meters (415V Three-Phase (UK / Australia Industrial))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 10 A over 60 m (196.9 ft).
Copper Cable (≤3% Drop)2.5 mm²Drop: 8.9V (2.14%)
Aluminum Cable (≤3% Drop)4 mm²Drop: 9.17V (2.21%)
Voltage at Load406.1 VLine Loss: 154.1 W
Max Power & Breaker7.19 kW10A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 10A at 60m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 14.83 V (3.57%) | 400.2 V | 24.46 V (5.89%) | 256.8 W | ~ ≤5% |
| 2.5 mm² | 24 A | 18 A | 8.9 V (2.14%) | 406.1 V | 14.67 V (3.54%) | 154.1 W | ✓ OK (≤3%) |
| 4 mm² | 32 A | 25 A | 5.56 V (1.34%) | 409.4 V | 9.17 V (2.21%) | 96.3 W | ✓ OK (≤3%) |
| 6 mm² | 41 A | 32 A | 3.71 V (0.89%) | 411.3 V | 6.11 V (1.47%) | 64.2 W | ✓ OK (≤3%) |
| 10 mm² | 57 A | 44 A | 2.22 V (0.54%) | 412.8 V | 3.67 V (0.88%) | 38.5 W | ✓ OK (≤3%) |
| 16 mm² | 76 A | 59 A | 1.39 V (0.33%) | 413.6 V | 2.29 V (0.55%) | 24.1 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 0.89 V (0.21%) | 414.1 V | 1.47 V (0.35%) | 15.4 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 0.64 V (0.15%) | 414.4 V | 1.05 V (0.25%) | 11.0 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 0.44 V (0.11%) | 414.6 V | 0.73 V (0.18%) | 7.7 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.32 V (0.08%) | 414.7 V | 0.52 V (0.13%) | 5.5 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.23 V (0.06%) | 414.8 V | 0.39 V (0.09%) | 4.1 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.19 V (0.04%) | 414.8 V | 0.31 V (0.07%) | 3.2 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.15 V (0.04%) | 414.9 V | 0.24 V (0.06%) | 2.6 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.12 V (0.03%) | 414.9 V | 0.2 V (0.05%) | 2.1 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.09 V (0.02%) | 414.9 V | 0.15 V (0.04%) | 1.6 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.07 V (0.02%) | 414.9 V | 0.12 V (0.03%) | 1.3 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.06 V (0.01%) | 414.9 V | 0.09 V (0.02%) | 1.0 W | ✓ OK (≤3%) |
FAQ — 10 Amp Cable Size at 60 Meters (415V Three-Phase (UK / Australia Industrial))
What mm² cable size is required for 10A at 60 meters (415V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2.5 mm² copper cable for 10A over 60m at 415V (voltage drop: 8.9V or 2.14%).
What is the power capacity of 10A at 415V?
At unity power factor, 10A at 415V supports 7.19 kW with a standard 10A circuit breaker.
Related Lengths & Currents (415V)
10A · 5m (415V)10A · 10m (415V)10A · 15m (415V)10A · 20m (415V)10A · 25m (415V)10A · 30m (415V)10A · 35m (415V)10A · 40m (415V)10A · 45m (415V)10A · 50m (415V)10A · 70m (415V)16A · 60m (415V)20A · 60m (415V)25A · 60m (415V)32A · 60m (415V)40A · 60m (415V)50A · 60m (415V)63A · 60m (415V)80A · 60m (415V)100A · 60m (415V)125A · 60m (415V)160A · 60m (415V)200A · 60m (415V)