100 Amp Cable Size at 100 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 100 A over 100 m (328.1 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 1.43V (2.97%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.76V (3.68%)
Voltage at Load46.6 VLine Loss: 142.7 W
Max Power & Breaker4.8 kW100A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 100A at 100m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A285.33 V (594.44%)0.0 V470.67 V (980.56%)28533.3 WDrop High
2.5 mm²24 A18 A171.2 V (356.67%)0.0 V282.4 V (588.33%)17120.0 WDrop High
4 mm²32 A25 A107.0 V (222.92%)0.0 V176.5 V (367.71%)10700.0 WDrop High
6 mm²41 A32 A71.33 V (148.61%)0.0 V117.67 V (245.14%)7133.3 WDrop High
10 mm²57 A44 A42.8 V (89.17%)5.2 V70.6 V (147.08%)4280.0 WDrop High
16 mm²76 A59 A26.75 V (55.73%)21.3 V44.12 V (91.93%)2675.0 WDrop High
25 mm²101 A78 A17.12 V (35.67%)30.9 V28.24 V (58.83%)1712.0 WDrop High
35 mm²125 A97 A12.23 V (25.48%)35.8 V20.17 V (42.02%)1222.9 WDrop High
50 mm²151 A118 A8.56 V (17.83%)39.4 V14.12 V (29.42%)856.0 WDrop High
70 mm²192 A150 A6.11 V (12.74%)41.9 V10.09 V (21.01%)611.4 WDrop High
95 mm²232 A181 A4.51 V (9.39%)43.5 V7.43 V (15.48%)450.5 WDrop High
120 mm²269 A210 A3.57 V (7.43%)44.4 V5.88 V (12.26%)356.7 WDrop High
150 mm²309 A241 A2.85 V (5.94%)45.1 V4.71 V (9.81%)285.3 WDrop High
185 mm²353 A275 A2.31 V (4.82%)45.7 V3.82 V (7.95%)231.4 W~ ≤5%
240 mm²415 A324 A1.78 V (3.72%)46.2 V2.94 V (6.13%)178.3 W~ ≤5%
300 mm²477 A372 A1.43 V (2.97%)46.6 V2.35 V (4.9%)142.7 W✓ OK (≤3%)
400 mm²570 A445 A1.07 V (2.23%)46.9 V1.76 V (3.68%)107.0 W✓ OK (≤3%)

FAQ — 100 Amp Cable Size at 100 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 100A at 100 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 100A over 100m at 48V (voltage drop: 1.43V or 2.97%).

What is the power capacity of 100A at 48V?

At unity power factor, 100A at 48V supports 4.8 kW with a standard 100A circuit breaker.