16 Amp Cable Size at 100 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 16 A over 100 m (328.1 ft).

Copper Cable (≤3% Drop)50 mm²Drop: 1.37V (2.85%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 1.19V (2.48%)
Voltage at Load46.6 VLine Loss: 21.9 W
Max Power & Breaker0.77 kW16A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 100m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A45.65 V (95.11%)2.3 V75.31 V (156.89%)730.5 WDrop High
2.5 mm²24 A18 A27.39 V (57.07%)20.6 V45.18 V (94.13%)438.3 WDrop High
4 mm²32 A25 A17.12 V (35.67%)30.9 V28.24 V (58.83%)273.9 WDrop High
6 mm²41 A32 A11.41 V (23.78%)36.6 V18.83 V (39.22%)182.6 WDrop High
10 mm²57 A44 A6.85 V (14.27%)41.2 V11.3 V (23.53%)109.6 WDrop High
16 mm²76 A59 A4.28 V (8.92%)43.7 V7.06 V (14.71%)68.5 WDrop High
25 mm²101 A78 A2.74 V (5.71%)45.3 V4.52 V (9.41%)43.8 WDrop High
35 mm²125 A97 A1.96 V (4.08%)46.0 V3.23 V (6.72%)31.3 W~ ≤5%
50 mm²151 A118 A1.37 V (2.85%)46.6 V2.26 V (4.71%)21.9 W✓ OK (≤3%)
70 mm²192 A150 A0.98 V (2.04%)47.0 V1.61 V (3.36%)15.7 W✓ OK (≤3%)
95 mm²232 A181 A0.72 V (1.5%)47.3 V1.19 V (2.48%)11.5 W✓ OK (≤3%)
120 mm²269 A210 A0.57 V (1.19%)47.4 V0.94 V (1.96%)9.1 W✓ OK (≤3%)
150 mm²309 A241 A0.46 V (0.95%)47.5 V0.75 V (1.57%)7.3 W✓ OK (≤3%)
185 mm²353 A275 A0.37 V (0.77%)47.6 V0.61 V (1.27%)5.9 W✓ OK (≤3%)
240 mm²415 A324 A0.29 V (0.59%)47.7 V0.47 V (0.98%)4.6 W✓ OK (≤3%)
300 mm²477 A372 A0.23 V (0.48%)47.8 V0.38 V (0.78%)3.7 W✓ OK (≤3%)
400 mm²570 A445 A0.17 V (0.36%)47.8 V0.28 V (0.59%)2.7 W✓ OK (≤3%)

FAQ — 16 Amp Cable Size at 100 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 16A at 100 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 50 mm² copper cable for 16A over 100m at 48V (voltage drop: 1.37V or 2.85%).

What is the power capacity of 16A at 48V?

At unity power factor, 16A at 48V supports 0.77 kW with a standard 16A circuit breaker.