63 Amp Cable Size at 20 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 63 A over 20 m (65.6 ft).

Copper Cable (≤3% Drop)16 mm²Drop: 2.92V (0.7%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 3.08V (0.74%)
Voltage at Load412.1 VLine Loss: 318.5 W
Max Power & Breaker45.28 kW63A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 63A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A31.14 V (7.5%)383.9 V51.36 V (12.38%)3397.5 WDrop High
2.5 mm²24 A18 A18.68 V (4.5%)396.3 V30.82 V (7.43%)2038.5 WDrop High
4 mm²32 A25 A11.68 V (2.81%)403.3 V19.26 V (4.64%)1274.0 WDrop High
6 mm²41 A32 A7.78 V (1.88%)407.2 V12.84 V (3.09%)849.4 WDrop High
10 mm²57 A44 A4.67 V (1.13%)410.3 V7.7 V (1.86%)509.6 WDrop High
16 mm²76 A59 A2.92 V (0.7%)412.1 V4.81 V (1.16%)318.5 W✓ OK (≤3%)
25 mm²101 A78 A1.87 V (0.45%)413.1 V3.08 V (0.74%)203.8 W✓ OK (≤3%)
35 mm²125 A97 A1.33 V (0.32%)413.7 V2.2 V (0.53%)145.6 W✓ OK (≤3%)
50 mm²151 A118 A0.93 V (0.23%)414.1 V1.54 V (0.37%)101.9 W✓ OK (≤3%)
70 mm²192 A150 A0.67 V (0.16%)414.3 V1.1 V (0.27%)72.8 W✓ OK (≤3%)
95 mm²232 A181 A0.49 V (0.12%)414.5 V0.81 V (0.2%)53.6 W✓ OK (≤3%)
120 mm²269 A210 A0.39 V (0.09%)414.6 V0.64 V (0.15%)42.5 W✓ OK (≤3%)
150 mm²309 A241 A0.31 V (0.08%)414.7 V0.51 V (0.12%)34.0 W✓ OK (≤3%)
185 mm²353 A275 A0.25 V (0.06%)414.7 V0.42 V (0.1%)27.5 W✓ OK (≤3%)
240 mm²415 A324 A0.19 V (0.05%)414.8 V0.32 V (0.08%)21.2 W✓ OK (≤3%)
300 mm²477 A372 A0.16 V (0.04%)414.8 V0.26 V (0.06%)17.0 W✓ OK (≤3%)
400 mm²570 A445 A0.12 V (0.03%)414.9 V0.19 V (0.05%)12.7 W✓ OK (≤3%)

FAQ — 63 Amp Cable Size at 20 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 63A at 20 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 16 mm² copper cable for 63A over 20m at 415V (voltage drop: 2.92V or 0.7%).

What is the power capacity of 63A at 415V?

At unity power factor, 63A at 415V supports 45.28 kW with a standard 63A circuit breaker.