125 Amp Cable Size at 20 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 125 A over 20 m (65.6 ft).

Copper Cable (≤3% Drop)35 mm²Drop: 2.65V (0.64%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 2.18V (0.53%)
Voltage at Load412.4 VLine Loss: 573.2 W
Max Power & Breaker89.85 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A61.78 V (14.89%)353.2 V101.9 V (24.55%)13375.0 WDrop High
2.5 mm²24 A18 A37.07 V (8.93%)377.9 V61.14 V (14.73%)8025.0 WDrop High
4 mm²32 A25 A23.17 V (5.58%)391.8 V38.21 V (9.21%)5015.6 WDrop High
6 mm²41 A32 A15.44 V (3.72%)399.6 V25.48 V (6.14%)3343.8 WDrop High
10 mm²57 A44 A9.27 V (2.23%)405.7 V15.29 V (3.68%)2006.2 WDrop High
16 mm²76 A59 A5.79 V (1.4%)409.2 V9.55 V (2.3%)1253.9 WDrop High
25 mm²101 A78 A3.71 V (0.89%)411.3 V6.11 V (1.47%)802.5 WDrop High
35 mm²125 A97 A2.65 V (0.64%)412.4 V4.37 V (1.05%)573.2 W✓ OK (≤3%)
50 mm²151 A118 A1.85 V (0.45%)413.1 V3.06 V (0.74%)401.2 W✓ OK (≤3%)
70 mm²192 A150 A1.32 V (0.32%)413.7 V2.18 V (0.53%)286.6 W✓ OK (≤3%)
95 mm²232 A181 A0.98 V (0.24%)414.0 V1.61 V (0.39%)211.2 W✓ OK (≤3%)
120 mm²269 A210 A0.77 V (0.19%)414.2 V1.27 V (0.31%)167.2 W✓ OK (≤3%)
150 mm²309 A241 A0.62 V (0.15%)414.4 V1.02 V (0.25%)133.8 W✓ OK (≤3%)
185 mm²353 A275 A0.5 V (0.12%)414.5 V0.83 V (0.2%)108.4 W✓ OK (≤3%)
240 mm²415 A324 A0.39 V (0.09%)414.6 V0.64 V (0.15%)83.6 W✓ OK (≤3%)
300 mm²477 A372 A0.31 V (0.07%)414.7 V0.51 V (0.12%)66.9 W✓ OK (≤3%)
400 mm²570 A445 A0.23 V (0.06%)414.8 V0.38 V (0.09%)50.2 W✓ OK (≤3%)

FAQ — 125 Amp Cable Size at 20 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 125A at 20 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 35 mm² copper cable for 125A over 20m at 415V (voltage drop: 2.65V or 0.64%).

What is the power capacity of 125A at 415V?

At unity power factor, 125A at 415V supports 89.85 kW with a standard 125A circuit breaker.