100 Amp Cable Size at 250 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 100 A over 250 m (820.2 ft).

Copper Cable (≤3% Drop)4× 400 mm²Drop: 0.67V (2.79%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 4.41V (18.39%)
Voltage at Load23.3 VLine Loss: 66.9 W
Max Power & Breaker2.4 kW100A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 100A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A713.33 V (2972.22%)0.0 V1176.67 V (4902.78%)71333.3 WDrop High
2.5 mm²24 A18 A428.0 V (1783.33%)0.0 V706.0 V (2941.67%)42800.0 WDrop High
4 mm²32 A25 A267.5 V (1114.58%)0.0 V441.25 V (1838.54%)26750.0 WDrop High
6 mm²41 A32 A178.33 V (743.06%)0.0 V294.17 V (1225.69%)17833.3 WDrop High
10 mm²57 A44 A107.0 V (445.83%)0.0 V176.5 V (735.42%)10700.0 WDrop High
16 mm²76 A59 A66.88 V (278.65%)0.0 V110.31 V (459.64%)6687.5 WDrop High
25 mm²101 A78 A42.8 V (178.33%)0.0 V70.6 V (294.17%)4280.0 WDrop High
35 mm²125 A97 A30.57 V (127.38%)0.0 V50.43 V (210.12%)3057.1 WDrop High
50 mm²151 A118 A21.4 V (89.17%)2.6 V35.3 V (147.08%)2140.0 WDrop High
70 mm²192 A150 A15.29 V (63.69%)8.7 V25.21 V (105.06%)1528.6 WDrop High
95 mm²232 A181 A11.26 V (46.93%)12.7 V18.58 V (77.41%)1126.3 WDrop High
120 mm²269 A210 A8.92 V (37.15%)15.1 V14.71 V (61.28%)891.7 WDrop High
150 mm²309 A241 A7.13 V (29.72%)16.9 V11.77 V (49.03%)713.3 WDrop High
185 mm²353 A275 A5.78 V (24.1%)18.2 V9.54 V (39.75%)578.4 WDrop High
240 mm²415 A324 A4.46 V (18.58%)19.5 V7.35 V (30.64%)445.8 WDrop High
300 mm²477 A372 A3.57 V (14.86%)20.4 V5.88 V (24.51%)356.7 WDrop High
400 mm²570 A445 A2.67 V (11.15%)21.3 V4.41 V (18.39%)267.5 WDrop High

FAQ — 100 Amp Cable Size at 250 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 100A at 250 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 4× 400 mm² copper cable for 100A over 250m at 24V (voltage drop: 0.67V or 2.79%).

What is the power capacity of 100A at 24V?

At unity power factor, 100A at 24V supports 2.4 kW with a standard 100A circuit breaker.