⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

125 Amp Cable Size at 250 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 125 A over 250 m (820.2 ft).

Copper Cable (≤3% Drop)5× 400 mm²Drop: 0.67V (2.79%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 5.52V (22.98%)
Voltage at Load23.3 VLine Loss: 83.6 W
Max Power & Breaker3.0 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A891.67 V (3715.28%)0.0 V1470.83 V (6128.47%)111458.3 WDrop High
2.5 mm²24 A18 A535.0 V (2229.17%)0.0 V882.5 V (3677.08%)66875.0 WDrop High
4 mm²32 A25 A334.38 V (1393.23%)0.0 V551.56 V (2298.18%)41796.9 WDrop High
6 mm²41 A32 A222.92 V (928.82%)0.0 V367.71 V (1532.12%)27864.6 WDrop High
10 mm²57 A44 A133.75 V (557.29%)0.0 V220.62 V (919.27%)16718.7 WDrop High
16 mm²76 A59 A83.59 V (348.31%)0.0 V137.89 V (574.54%)10449.2 WDrop High
25 mm²101 A78 A53.5 V (222.92%)0.0 V88.25 V (367.71%)6687.5 WDrop High
35 mm²125 A97 A38.21 V (159.23%)0.0 V63.04 V (262.65%)4776.8 WDrop High
50 mm²151 A118 A26.75 V (111.46%)0.0 V44.12 V (183.85%)3343.8 WDrop High
70 mm²192 A150 A19.11 V (79.61%)4.9 V31.52 V (131.32%)2388.4 WDrop High
95 mm²232 A181 A14.08 V (58.66%)9.9 V23.22 V (96.77%)1759.9 WDrop High
120 mm²269 A210 A11.15 V (46.44%)12.9 V18.39 V (76.61%)1393.2 WDrop High
150 mm²309 A241 A8.92 V (37.15%)15.1 V14.71 V (61.28%)1114.6 WDrop High
185 mm²353 A275 A7.23 V (30.12%)16.8 V11.93 V (49.69%)903.7 WDrop High
240 mm²415 A324 A5.57 V (23.22%)18.4 V9.19 V (38.3%)696.6 WDrop High
300 mm²477 A372 A4.46 V (18.58%)19.5 V7.35 V (30.64%)557.3 WDrop High
400 mm²570 A445 A3.34 V (13.93%)20.7 V5.52 V (22.98%)418.0 WDrop High

FAQ — 125 Amp Cable Size at 250 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 125A at 250 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 5× 400 mm² copper cable for 125A over 250m at 24V (voltage drop: 0.67V or 2.79%).

What is the power capacity of 125A at 24V?

At unity power factor, 125A at 24V supports 3.0 kW with a standard 125A circuit breaker.