16 Amp Cable Size at 250 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 16 A over 250 m (820.2 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 0.71V (2.97%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 0.71V (2.94%)
Voltage at Load23.3 VLine Loss: 11.4 W
Max Power & Breaker0.38 kW16A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A114.13 V (475.56%)0.0 V188.27 V (784.44%)1826.1 WDrop High
2.5 mm²24 A18 A68.48 V (285.33%)0.0 V112.96 V (470.67%)1095.7 WDrop High
4 mm²32 A25 A42.8 V (178.33%)0.0 V70.6 V (294.17%)684.8 WDrop High
6 mm²41 A32 A28.53 V (118.89%)0.0 V47.07 V (196.11%)456.5 WDrop High
10 mm²57 A44 A17.12 V (71.33%)6.9 V28.24 V (117.67%)273.9 WDrop High
16 mm²76 A59 A10.7 V (44.58%)13.3 V17.65 V (73.54%)171.2 WDrop High
25 mm²101 A78 A6.85 V (28.53%)17.2 V11.3 V (47.07%)109.6 WDrop High
35 mm²125 A97 A4.89 V (20.38%)19.1 V8.07 V (33.62%)78.3 WDrop High
50 mm²151 A118 A3.42 V (14.27%)20.6 V5.65 V (23.53%)54.8 WDrop High
70 mm²192 A150 A2.45 V (10.19%)21.6 V4.03 V (16.81%)39.1 WDrop High
95 mm²232 A181 A1.8 V (7.51%)22.2 V2.97 V (12.39%)28.8 WDrop High
120 mm²269 A210 A1.43 V (5.94%)22.6 V2.35 V (9.81%)22.8 WDrop High
150 mm²309 A241 A1.14 V (4.76%)22.9 V1.88 V (7.84%)18.3 W~ ≤5%
185 mm²353 A275 A0.93 V (3.86%)23.1 V1.53 V (6.36%)14.8 W~ ≤5%
240 mm²415 A324 A0.71 V (2.97%)23.3 V1.18 V (4.9%)11.4 W✓ OK (≤3%)
300 mm²477 A372 A0.57 V (2.38%)23.4 V0.94 V (3.92%)9.1 W✓ OK (≤3%)
400 mm²570 A445 A0.43 V (1.78%)23.6 V0.71 V (2.94%)6.8 W✓ OK (≤3%)

FAQ — 16 Amp Cable Size at 250 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 16A at 250 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 16A over 250m at 24V (voltage drop: 0.71V or 2.97%).

What is the power capacity of 16A at 24V?

At unity power factor, 16A at 24V supports 0.38 kW with a standard 16A circuit breaker.