1000 Amp Cable Size at 150 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 1000 A over 150 m (492.1 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 6.95V (1.74%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 22.93V (5.73%)
Voltage at Load393.1 VLine Loss: 12037.5 W
Max Power & Breaker692.82 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 1000A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3706.59 V (926.65%)0.0 V6114.14 V (1528.53%)6420000.0 WDrop High
2.5 mm²24 A18 A2223.95 V (555.99%)0.0 V3668.48 V (917.12%)3852000.0 WDrop High
4 mm²32 A25 A1389.97 V (347.49%)0.0 V2292.8 V (573.2%)2407500.0 WDrop High
6 mm²41 A32 A926.65 V (231.66%)0.0 V1528.53 V (382.13%)1605000.0 WDrop High
10 mm²57 A44 A555.99 V (139.0%)0.0 V917.12 V (229.28%)963000.0 WDrop High
16 mm²76 A59 A347.49 V (86.87%)52.5 V573.2 V (143.3%)601875.0 WDrop High
25 mm²101 A78 A222.4 V (55.6%)177.6 V366.85 V (91.71%)385200.0 WDrop High
35 mm²125 A97 A158.85 V (39.71%)241.1 V262.03 V (65.51%)275142.9 WDrop High
50 mm²151 A118 A111.2 V (27.8%)288.8 V183.42 V (45.86%)192600.0 WDrop High
70 mm²192 A150 A79.43 V (19.86%)320.6 V131.02 V (32.75%)137571.4 WDrop High
95 mm²232 A181 A58.53 V (14.63%)341.5 V96.54 V (24.13%)101368.4 WDrop High
120 mm²269 A210 A46.33 V (11.58%)353.7 V76.43 V (19.11%)80250.0 WDrop High
150 mm²309 A241 A37.07 V (9.27%)362.9 V61.14 V (15.29%)64200.0 WDrop High
185 mm²353 A275 A30.05 V (7.51%)369.9 V49.57 V (12.39%)52054.1 WDrop High
240 mm²415 A324 A23.17 V (5.79%)376.8 V38.21 V (9.55%)40125.0 WDrop High
300 mm²477 A372 A18.53 V (4.63%)381.5 V30.57 V (7.64%)32100.0 WDrop High
400 mm²570 A445 A13.9 V (3.47%)386.1 V22.93 V (5.73%)24075.0 WDrop High

FAQ — 1000 Amp Cable Size at 150 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 1000A at 150 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 1000A over 150m at 400V (voltage drop: 6.95V or 1.74%).

What is the power capacity of 1000A at 400V?

At unity power factor, 1000A at 400V supports 692.82 kW with a standard 1000A circuit breaker.