1000 Amp Cable Size at 200 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 1000 A over 200 m (656.2 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 9.27V (1.34%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 30.57V (4.43%)
Voltage at Load680.7 VLine Loss: 16050.0 W
Max Power & Breaker1195.12 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 1000A at 200m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A4942.12 V (716.25%)0.0 V8152.19 V (1181.48%)8560000.0 WDrop High
2.5 mm²24 A18 A2965.27 V (429.75%)0.0 V4891.31 V (708.89%)5136000.0 WDrop High
4 mm²32 A25 A1853.29 V (268.59%)0.0 V3057.07 V (443.05%)3210000.0 WDrop High
6 mm²41 A32 A1235.53 V (179.06%)0.0 V2038.05 V (295.37%)2140000.0 WDrop High
10 mm²57 A44 A741.32 V (107.44%)0.0 V1222.83 V (177.22%)1284000.0 WDrop High
16 mm²76 A59 A463.32 V (67.15%)226.7 V764.27 V (110.76%)802500.0 WDrop High
25 mm²101 A78 A296.53 V (42.97%)393.5 V489.13 V (70.89%)513600.0 WDrop High
35 mm²125 A97 A211.81 V (30.7%)478.2 V349.38 V (50.63%)366857.1 WDrop High
50 mm²151 A118 A148.26 V (21.49%)541.7 V244.57 V (35.44%)256800.0 WDrop High
70 mm²192 A150 A105.9 V (15.35%)584.1 V174.69 V (25.32%)183428.6 WDrop High
95 mm²232 A181 A78.03 V (11.31%)612.0 V128.72 V (18.65%)135157.9 WDrop High
120 mm²269 A210 A61.78 V (8.95%)628.2 V101.9 V (14.77%)107000.0 WDrop High
150 mm²309 A241 A49.42 V (7.16%)640.6 V81.52 V (11.81%)85600.0 WDrop High
185 mm²353 A275 A40.07 V (5.81%)649.9 V66.1 V (9.58%)69405.4 WDrop High
240 mm²415 A324 A30.89 V (4.48%)659.1 V50.95 V (7.38%)53500.0 WDrop High
300 mm²477 A372 A24.71 V (3.58%)665.3 V40.76 V (5.91%)42800.0 WDrop High
400 mm²570 A445 A18.53 V (2.69%)671.5 V30.57 V (4.43%)32100.0 WDrop High

FAQ — 1000 Amp Cable Size at 200 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 1000A at 200 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 1000A over 200m at 690V (voltage drop: 9.27V or 1.34%).

What is the power capacity of 1000A at 690V?

At unity power factor, 1000A at 690V supports 1195.12 kW with a standard 1000A circuit breaker.