⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

1000 Amp Cable Size at 50 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 1000 A over 50 m (164.0 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 2.31V (0.34%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 7.64V (1.11%)
Voltage at Load687.7 VLine Loss: 4012.5 W
Max Power & Breaker1195.12 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 1000A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1235.53 V (179.06%)0.0 V2038.05 V (295.37%)2140000.0 WDrop High
2.5 mm²24 A18 A741.32 V (107.44%)0.0 V1222.83 V (177.22%)1284000.0 WDrop High
4 mm²32 A25 A463.32 V (67.15%)226.7 V764.27 V (110.76%)802500.0 WDrop High
6 mm²41 A32 A308.88 V (44.77%)381.1 V509.51 V (73.84%)535000.0 WDrop High
10 mm²57 A44 A185.33 V (26.86%)504.7 V305.71 V (44.31%)321000.0 WDrop High
16 mm²76 A59 A115.83 V (16.79%)574.2 V191.07 V (27.69%)200625.0 WDrop High
25 mm²101 A78 A74.13 V (10.74%)615.9 V122.28 V (17.72%)128400.0 WDrop High
35 mm²125 A97 A52.95 V (7.67%)637.0 V87.34 V (12.66%)91714.3 WDrop High
50 mm²151 A118 A37.07 V (5.37%)652.9 V61.14 V (8.86%)64200.0 WDrop High
70 mm²192 A150 A26.48 V (3.84%)663.5 V43.67 V (6.33%)45857.1 WDrop High
95 mm²232 A181 A19.51 V (2.83%)670.5 V32.18 V (4.66%)33789.5 WDrop High
120 mm²269 A210 A15.44 V (2.24%)674.6 V25.48 V (3.69%)26750.0 WDrop High
150 mm²309 A241 A12.36 V (1.79%)677.6 V20.38 V (2.95%)21400.0 WDrop High
185 mm²353 A275 A10.02 V (1.45%)680.0 V16.52 V (2.39%)17351.4 WDrop High
240 mm²415 A324 A7.72 V (1.12%)682.3 V12.74 V (1.85%)13375.0 WDrop High
300 mm²477 A372 A6.18 V (0.9%)683.8 V10.19 V (1.48%)10700.0 WDrop High
400 mm²570 A445 A4.63 V (0.67%)685.4 V7.64 V (1.11%)8025.0 WDrop High

FAQ — 1000 Amp Cable Size at 50 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 1000A at 50 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 1000A over 50m at 690V (voltage drop: 2.31V or 0.34%).

What is the power capacity of 1000A at 690V?

At unity power factor, 1000A at 690V supports 1195.12 kW with a standard 1000A circuit breaker.