1000 Amp Cable Size at 70 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 1000 A over 70 m (229.7 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 3.25V (0.47%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 10.7V (1.55%)
Voltage at Load686.8 VLine Loss: 5617.5 W
Max Power & Breaker1195.12 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 1000A at 70m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1729.74 V (250.69%)0.0 V2853.27 V (413.52%)2996000.0 WDrop High
2.5 mm²24 A18 A1037.84 V (150.41%)0.0 V1711.96 V (248.11%)1797600.0 WDrop High
4 mm²32 A25 A648.65 V (94.01%)41.3 V1069.97 V (155.07%)1123500.0 WDrop High
6 mm²41 A32 A432.44 V (62.67%)257.6 V713.32 V (103.38%)749000.0 WDrop High
10 mm²57 A44 A259.46 V (37.6%)430.5 V427.99 V (62.03%)449400.0 WDrop High
16 mm²76 A59 A162.16 V (23.5%)527.8 V267.49 V (38.77%)280875.0 WDrop High
25 mm²101 A78 A103.78 V (15.04%)586.2 V171.2 V (24.81%)179760.0 WDrop High
35 mm²125 A97 A74.13 V (10.74%)615.9 V122.28 V (17.72%)128400.0 WDrop High
50 mm²151 A118 A51.89 V (7.52%)638.1 V85.6 V (12.41%)89880.0 WDrop High
70 mm²192 A150 A37.07 V (5.37%)652.9 V61.14 V (8.86%)64200.0 WDrop High
95 mm²232 A181 A27.31 V (3.96%)662.7 V45.05 V (6.53%)47305.3 WDrop High
120 mm²269 A210 A21.62 V (3.13%)668.4 V35.67 V (5.17%)37450.0 WDrop High
150 mm²309 A241 A17.3 V (2.51%)672.7 V28.53 V (4.14%)29960.0 WDrop High
185 mm²353 A275 A14.02 V (2.03%)676.0 V23.13 V (3.35%)24291.9 WDrop High
240 mm²415 A324 A10.81 V (1.57%)679.2 V17.83 V (2.58%)18725.0 WDrop High
300 mm²477 A372 A8.65 V (1.25%)681.4 V14.27 V (2.07%)14980.0 WDrop High
400 mm²570 A445 A6.49 V (0.94%)683.5 V10.7 V (1.55%)11235.0 WDrop High

FAQ — 1000 Amp Cable Size at 70 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 1000A at 70 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 1000A over 70m at 690V (voltage drop: 3.25V or 0.47%).

What is the power capacity of 1000A at 690V?

At unity power factor, 1000A at 690V supports 1195.12 kW with a standard 1000A circuit breaker.