1000 Amp Cable Size at 5 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 1000 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 0.27V (1.11%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 0.88V (3.68%)
Voltage at Load23.7 VLine Loss: 267.5 W
Max Power & Breaker24.0 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 1000A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A142.67 V (594.44%)0.0 V235.33 V (980.56%)142666.7 WDrop High
2.5 mm²24 A18 A85.6 V (356.67%)0.0 V141.2 V (588.33%)85600.0 WDrop High
4 mm²32 A25 A53.5 V (222.92%)0.0 V88.25 V (367.71%)53500.0 WDrop High
6 mm²41 A32 A35.67 V (148.61%)0.0 V58.83 V (245.14%)35666.7 WDrop High
10 mm²57 A44 A21.4 V (89.17%)2.6 V35.3 V (147.08%)21400.0 WDrop High
16 mm²76 A59 A13.38 V (55.73%)10.6 V22.06 V (91.93%)13375.0 WDrop High
25 mm²101 A78 A8.56 V (35.67%)15.4 V14.12 V (58.83%)8560.0 WDrop High
35 mm²125 A97 A6.11 V (25.48%)17.9 V10.09 V (42.02%)6114.3 WDrop High
50 mm²151 A118 A4.28 V (17.83%)19.7 V7.06 V (29.42%)4280.0 WDrop High
70 mm²192 A150 A3.06 V (12.74%)20.9 V5.04 V (21.01%)3057.1 WDrop High
95 mm²232 A181 A2.25 V (9.39%)21.7 V3.72 V (15.48%)2252.6 WDrop High
120 mm²269 A210 A1.78 V (7.43%)22.2 V2.94 V (12.26%)1783.3 WDrop High
150 mm²309 A241 A1.43 V (5.94%)22.6 V2.35 V (9.81%)1426.7 WDrop High
185 mm²353 A275 A1.16 V (4.82%)22.8 V1.91 V (7.95%)1156.8 WDrop High
240 mm²415 A324 A0.89 V (3.72%)23.1 V1.47 V (6.13%)891.7 WDrop High
300 mm²477 A372 A0.71 V (2.97%)23.3 V1.18 V (4.9%)713.3 WDrop High
400 mm²570 A445 A0.54 V (2.23%)23.5 V0.88 V (3.68%)535.0 WDrop High

FAQ — 1000 Amp Cable Size at 5 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 1000A at 5 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 1000A over 5m at 24V (voltage drop: 0.27V or 1.11%).

What is the power capacity of 1000A at 24V?

At unity power factor, 1000A at 24V supports 24.0 kW with a standard 1000A circuit breaker.